Section 8 - Micropanel
Form QTC4-NM2
Issue date: 05/12/2023
Table 27 -
Setpoint limits
Program value
Mode
Low limit
High limit
Default
Leaving chilled liquid setpoint
Water cooling
40.0°F
60.0°F
44.0°F
4.4°C
15.6°C
6.7°C
Glycol cooling
15.0°F
70.0°F
44.0°F
-9.4°C
15.6°C
6.7°C
Leaving chilled liquid control range
–
1.5°F
2.5°F
2.0°F
0.8°C
1.4°C
1.1°C
Maximum remote temperature reset
–
2°F
40°F
20°F
1°C
22°C
11°C
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values
allowed under the SETPOINTS key are provided in
.