Qualitrol 118 Series Скачать руководство пользователя страница 14

Electronic Temperature Monitor 

E C N - 2 7 6 4 4  

1 3

 

J u l y   7 ,   2 0 1 0  

 

Configuration 

 

View / Change Config –

 Opens a screen that allows the entry of 

configuration information.  One can then download the configuration to an ETM 
and / or save it to a configuration file.  It is also possible to upload the existing 
configuration from the ETM to the Configuration screen 

The configuration Software allows the user to set up the following parameters of 
the ETM: 

 

Active Channels – Any one or 2 of the 3 input channels can be turned off, if 
they are not being used in an application. 

 

Fan / Alarm / Trip setpoint and switching differential (hyteteresis) can be set 
to determine at what temperature the relays turn on and off. 

 

Trip relay can be set to failsafe (normally energized) or not failsafe (normally 
de-energized). 

 

Fan Exerciser – the fan exerciser function can be turned ON or OFF.  When it 
is ON, the time between turning the fans on, and the run time can be set. 

 

SCADA Remote Output can be set to operate from hottest phase or only 
center phase. 

 

Reverse thermocouple sense feature can be activated or de-activated.  This 
allows an inadvertent sensor-wiring problem to be detected quickly.  If the 
thermocouple is connected incorrectly, as the temperature goes up, the display 
temperature goes down.  If the reverse thermocouple feature is activated, when 
the thermocouple reaches 30°C below the (internal) ambient temperature chip, 
the unit will go into “fault” mode.  In some instances a sudden increase in 
ambient, such as early morning sun shining on a unit where the transformer is 
still cold may cause the same result.  In this case the reverse thermocouple 
feature can be de-activated, and the unit will require a 70°C difference 
between the thermocouple and ambient to go into “fault” mode. 

 

The communications parameters for the optional RS-485 output can be set.   

 

Send configuration data to ETM – This will cause the displayed configuration 
data to be written to the ETM.  After the data is changed in the ETM memory, 
the ETM will reset to activate the new values. 

 

Get configuration data from ETM – This reads the configuration currently in 
the ETM and displays that data on the screen.  

 

Save – This will save the current configuration to the current open file (if it is 
the default file, it will overwrite it). 

 

Save as – Allows the current configuration to be saved to a new file name or 
different path. 

 

Done – exits this window. 

 

Print Configuration -

 Prints the configuration screen. 

Courtesy of NationalSwitchgear.com

Содержание 118 Series

Страница 1: ...Electronic Temperature Monitor for Dry Transformers 118 series Instruction Manual IST 054 1 Courtesy of NationalSwitchgear com...

Страница 2: ...QualiTROL 118 Series Electronic Temperature Monitor for Dry Type Transformers Instruction Manual Courtesy of NationalSwitchgear com...

Страница 3: ...___________________ 8 Temperature Display 8 Status Lamps 8 Alarm Audible 8 Push Buttons 8 Fan Exerciser 9 Functional Specification __________________________________________________________ 10 Setup S...

Страница 4: ...ntervals ON time and interval is programmable Operates a relay with a SPDT contact when one of the inputs exceeds the ALARM setting A RED LED indicates that the ALARM is ON An internal audible device...

Страница 5: ...ons to guide you through mounting supplying power to and wiring your Temperature Monitor Operation A description of use during transformer operation as well as easy instructions on how to perform a sy...

Страница 6: ...nitor The 118 mounts in a rectangular cutout in a panel and is secured by four 4 bolts See Figure 1 118 Dimensions Figure 1 118 Dimensions The 118H mounts in a rectangular cutout in a panel and is sec...

Страница 7: ...the internal temperature of the ETM If the channel is not used it can be turned OFF using the setup software but the terminals still need to be shorted together Relay Contacts FAN 1 The 1 fan contacts...

Страница 8: ...p Software section of this manual for more detailed information NOTE Wires should be connected to the RS 232 terminals only during parameter setup No permanent field wires should be connected to these...

Страница 9: ...e of the unit This provides a method of communicating with a remote master station using Modbus RTU protocol Refer to Appendix E of this manual for additional information See Figure 4 RS 485 Wiring Di...

Страница 10: ...larm An internal Buzzer sounds each time the ALARM becomes active The buzzer can be silenced by pressing the SILENCE push button The buzzer will then turn OFF and remain OFF until a new ALARM occurs P...

Страница 11: ...r The unit has a built in Fan Exerciser function that can turn the fans on for a short period of time at periodic intervals The default setting is for 1 minute every 7 days The Fan Exerciser can be co...

Страница 12: ...500 max load Accuracy 1 of full scale reading Fan Exerciser Fan Run Time 1 to 120 minutes Fan Cycle Time 0 01 to 30 0 days Time starts at power up Environment Operating Temperature 30 C to 72 C Stora...

Страница 13: ...are consists of these menu selections Installation Run SETUP BAT on the installation CD This will create a directory C QualiTROL on the hard drive and will install the program and default configuratio...

Страница 14: ...to be detected quickly If the thermocouple is connected incorrectly as the temperature goes up the display temperature goes down If the reverse thermocouple feature is activated when the thermocouple...

Страница 15: ...dual fuses Remote Output 0 0 1mA loop 4 4 20mA loop Thermocouple K Type K Voltage 120 120VAC 240 230 240VAC 277 277VAC Package P Panel mounting plate H Box with hinged front cover FAN turns ON at ____...

Страница 16: ...to step the Alarm setpoint up or down Push the MANUAL FAN button The TRIP light will be on and the display will show the Trip setpoint Use the AUDIBLE and MAX MEMORY buttons to step the Trip setpoint...

Страница 17: ...he fans turn ON If the unit is installed in an enclosure no further protection is required If the unit is mounted without being installed in an enclosure then to maintain the rated accuracy some form...

Страница 18: ...Electronic Temperature Monitor ECN 27644 17 July 7 2010 THERMOCOUPLE WIRE COPPER WIRE Model 118 ETM Millivolt Source ICE BATH Courtesy of NationalSwitchgear com...

Страница 19: ...lay Driver Continue to operate Failed Microprocessor Unit will not operate but failure is detected The FANS will turn ON and ALARM relay will be in the alarm state Intermittent sensor connection If th...

Страница 20: ...unit and within easy reach of the operator It shall be marked as the disconnecting device for the equipment Radio Frequency interference above Level 1 of EN 61000 4 6 conducted on the Mains wiring ma...

Страница 21: ...or they can be set up by the following procedure using front panel switches 1 Hold all three switches depressed until the unit stops cycling thru the readings approximately 10 seconds The unit will t...

Страница 22: ...hed for 30 seconds the unit will automatically return to normal operation with the communications setup unchanged Modbus Reg No Data Returned when Register Is addressed Comments 40001 40002 40003 Temp...

Страница 23: ...is disabled 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 Fan setpoint Alarm setpoint Trip setpoint Fan Switching differential hysteresis Alarm Switching differential hysteresis Trip Sw...

Отзывы: