Troubleshooting

5

With proper installation, operation, and maintenance your gas fireplace will
provide years of trouble-free service.  If you do experience a problem, this
troubleshooting guide will assist a qualified service person in the diagnosis
of a problem and the corrective action to be taken. This troubleshooting
guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1.

 After repeated

triggering of the red

or black piezo button,

the spark ignitor will

not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode wire is

properly connected, replace the ignitor.

b. Defective pilot or
misaligned electrode

(spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or
black piezo button again. If the pilot lights, an improper gas/air mixture caused the
bad lighting and a longer purge period is recommended. If the pilot will not light,

ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a
strong spark. If the gap is OK, replace the pilot.

c. No gas or low gas

pressure.

Check the remote shut-off valvess from the fireplace. Usually, there is a valve near

the gas main. There can be more than one (1) valve between the fireplace and the

main.

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.

  The pilot will not

stay lit after carefully

following the lighting

instructions.

a. Defective

thermocouple.

Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the

pilot for maximum flame impingement.

Ensure that the thermocouple connection at the gas valve is fully inserted and tight

(hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt meter lead wire on

the tip of the thermcouple and the other meter lead wire on the thermocouple

copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less

than 15mV, replace the thermocouple.

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

3.

 The pilot is

burning, there is no

gas burner, the valve

knob is in the ON
position, and the

ON/OFF switch is in

the ON position.

a. ON/OFF switch or
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the jumper
wires across the terminals at the switch. If the burner comes on, replace the
defective switch. If the switch is OK, place the jumper wires across the switch wires
at the gas valve. If the burner comes on, the wires are faulty or connections are

bad.

b. Thermopile may
not be generating

sufficient millivoltage.

If the pilot flame is not close enough physically to the thermopile, adjust the pilot

flame.

Be sure the wire connections from the thermopile at the gas valve terminals are

tight and that the thermopile is fully inserted into the pilot bracket.

Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP

terminals of the gas valve. The meter should read 325 millivolts minimum, while

holding the valve knob depressed in the pilot position, with the pilot lit, and the

ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is

below the specified minimum.

With the pilot in the ON position, disconnect the thermopile leads from the valve.
Take a reading at the thermopile leads. The reading should be 325 millivolts

minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON

position. Check the millivolt meter a the thermopile terminals. The millivolt meter

should read greater than 125mV. If the reading is acceptable, and if the burner
does not come on, replace the gas valve.

d. Plugged burner
orifice.

Check the burner orifice for stoppage. Remove stoppage.

e. Wall switch or
wires are defective.

Follow the corrective action in Symptom and Possible Cause 1.a above. Check

the switch and wiring. Replace where defective.

Содержание Village QVI35

Страница 1: ...not convertible for use with other gases unless a certified kit is used 1 Cet appareil peut tre install dans un mobile home pr fabriqu qui a t vendu et ne sera plus d plac si les codes locaux l autor...

Страница 2: ...lifi pour l inspection de l appareil et le remplacement de toute pi ce qui fut submerg e CET APPAREIL N EST P AS CON U POUR TRE UTILIS AVEC DES COMBUSTIBLES SOLIDES L installation et les r parations d...

Страница 3: ...AG de tout obstacle et mat riau afin d en permettre le service et le bon fonctionnement En raison de la temp rature lev e l appareil doit SE TROUVER en dehors des zones de passage et bonne distance de...

Страница 4: ...4 Section 5 Troubleshooting 36 Warranty 40 Table of Contents Consignes de s curit et mises en garde 2 Liste des pi ces de rechange 5 Section 1 Homologations et codes 10 Homologations et codes 10 Homol...

Страница 5: ...liste des num ros de pi ce se trouve la page suivante 10 6 9 11 7 12 13 14 4 5 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts QVI35 QVI30 Beginning Manufacturing Date 4 02 End...

Страница 6: ...in e 319 213A 14 Control Panel Panneau de configuration 319 119 Conversion Kit NG Module de conversion GN NGK QVI35 Conversion Kit LP Module de conversion PL LPK QVI35 Burner Orifice NG 32C Orifice de...

Страница 7: ...in e 319 213A 14 Control Panel Panneau de configuration 319 119 Conversion Kit NG Module de conversion GN NGK QVI30 Conversion Kit LP Module de conversion PL LPK QVI30 Burner Orifice NG 35C Orifice de...

Страница 8: ...h se de Valve 319 145 4 Tube Assembly Module de Tube 477 301A 5 Bottom Handle Poign e inf rieure 319 168 6 Top Handle Premi re Poign e 319 167 7 D Shaft D puits 319 836 8 Thermocouple Thermocouple 446...

Страница 9: ...og 2 B che 2 SRV330 702 SRV340 702 3 Log 3 B che 3 SRV330 703 SRV340 703 4 Log 4 B che 4 SRV340 705 SRV340 704 5 Log 5 B che 5 SRV330 704 SRV340 706 6 Log 6 B che 6 SRV330 706 SRV340 705 7 Log 7 B che...

Страница 10: ...g room in the U S A and Canada Homologation de l appareil Les mod les Quadra Fire dont il est question dans ce Guide d installation ont t test s conform ment aux normes d homologation et ont t approuv...

Страница 11: ...above 4 500 feet in Canada check with local authorities Installation haute altitude Les appareils gaz homologu s U L ont t test s et approuv s pour tre utilis s sans modification des altitudes compris...

Страница 12: ...n des appareils gaz Quadra Fire Les appareils gaz vacuation directe Quadra Fire sont con us pour aspirer tout l air de combustion de l ext rieur de l difice et expulser tous les gaz de combustion en d...

Страница 13: ...bustibles en ma onnerie ou pr fabriqu es combustible solide qui ont t install es conform ment aux codes de construction nationaux provinciaux et locaux 2 Les sp cifications d ouverture minimum de la...

Страница 14: ...d obtenir des performances une s curit et une efficacit optimales les cassettes doivent tre install es avec un rev tement de conduit approuv conform ment aux codes CAN CGA B 149 ou au code am ricain N...

Страница 15: ...ispositifs tels qu un interrupteur mural ou une commande distance Figure 1 Sch ma Comment d buter suite 6 1 16 153 8 2 19 32 65 9 A 5 5 32 130 7 2 5 16 58 4 2 5 32 54 9 C B 13 23 32 348 3 8 29 32 226...

Страница 16: ...TAGE WIRES FILS DE BASSE TENSION ON OFF SWITCH INTERRUPTEUR MARCHE ARRET MINIMUM APPLIANCE SIZE DIMENSIONS MINIMUM DE L APPAREIL Location QVI35 QVI30 Inches Milimeters Inches Milimeters A Front Width...

Страница 17: ...u syst me d vacuation Avant de commencer installer les modules d vacuation l installateur doit lire ces instructions et celles des modules d vacuation afin d obtenir une installation correcte Consulte...

Страница 18: ...a cassette suite REMARQUE Il sera peut tre n cessaire de d monter le registre de la chemin e en ma onnerie pour permettre l installation du conduit flexible AVERTISSEMENT LA CHEMIN E COMBUS TIBLE SOLI...

Страница 19: ...12 99 De 11 12 12 12 122 De 12 12 14 12 152 De 14 12 16 12 183 De 16 12 18 12 213 De 18 12 20 12 229 De 20 12 21 12 244 Installation de la cassette suite AVERTISSEMENT LES PRINCIPAUX CODES DE CONSTRUC...

Страница 20: ...llation de la cassette suite AVERTISSEMENT LE CONDUIT D VACUA TION DOIT TRE RACCORD SEULEMENT AU COLLET DE RACCORD DU SYST ME D VACUATION DE L APPAREIL ET AU COLLET CENTRAL DU CAPUCHON LE CONDUIT D AD...

Страница 21: ...NDUIT D ADMISSION D AIR TERMINATION CAP CAPUCHON ADAPTOR RACCORD EXHAUST COLLAR COLLET D EVACUATION INLET AIR COLLAR COLLET D ADMISSION D AIR STARTING COLLAR BRACKET COLLET DE RACCORD DU CONDUIT CROCH...

Страница 22: ...gure 7 Gas Controls Systems Figure 7 Syst mes de commande de gaz tape 2 Emplacement nivellement et solidification de la cassette Installation de la cassette suite 1 Placez la cassette l emplacement d...

Страница 23: ...par un technicien qualifi et ou muni d une licence de mani re re specter les r glements municipaux Dans la r publique de Massachusetts l installation doit tre effectu e par un plombier ou un installa...

Страница 24: ...r less than one half 1 2 psig 3 5 kPa Installing the Insert continued Step 5 Gas Pressure Requirements Installation de la cassette suite tape 5 Sp cifications de la pression du gaz Pression Gaz nature...

Страница 25: ...DIS TANCE SI VOUS VOUS ABSENTEZ POUR DES P RI ODES PROLONG ES DE CETTE FA ON LE FOYER NE POURRA PAS S ALLUMER ACCIDENTELLEMENT Filage de l allumage par veilleuse Sp cifications de l appareil Le foncti...

Страница 26: ...INTERRUP TEUR MURAL DE COMMANDE CELA D TRUIRAIT LA VALVE DE COMMANDE ATTENTION TIQUETEZ TOUS LES FILS AVANT DE LES D BRANCHER POUR LE SERVICE DES COM MANDES LES ERREURS DE FILAGE RISQUENT D ENTRA NER...

Страница 27: ...bs on the glass door into the slots on top of the firebox On the QVI35 slide the top tabs under the top spring latches Rotate the bottom of the glass door toward the firebox with slight upward pressur...

Страница 28: ...cement of the Ember Material 1 Soulevez la porte de garniture pour la retirer de l appareil 2 D verrouillez et retirez la porte en verre de l appareil Figure 10 Porte en verre Figure 12 Mise en place...

Страница 29: ...NITURE AVANT ET LA PORTE EN VERRE DE LA CASSETTE AVANT D INSTALLER L ENTOURAGE 1 Rep rez les fils de basse tension enroul s sur la cassette Voir Figure 13 2 Faites monter les fils de basse tension le...

Страница 30: ...ections above the gas fireplace Figure 14 La Figure 14 repr sente la dimension minimale verticale et la dimension maximale horizontale correspondante des habillages ou autres saillies combustibles au...

Страница 31: ...allumer l appareil Avant d allumer le foyer effectuez les op rations suivantes Revisez les consignes de s curit et les mises en garde Lisez la section Consignes de s curit et mises en garde au d but d...

Страница 32: ...e any part of the control system and any gas control which has been under water FOR YOUR SAFETY READ BEFORE LIGHTING WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RES...

Страница 33: ...inf rieure 2 Mettre le bouton de la valve de commande sur ARR T Tourner le bouton dans le sens horaire jusqu VEILLEUSE l enfoncer et con tinuer le tourner dans le sens horaire jusqu ARR T REMARQUE Le...

Страница 34: ...l utilisation et du type d installation il est conseill de demander un technicien de service qualifi d inspecter l appareil au d but de chaque saison de chauffage Vous trouverez ci dessous des directi...

Страница 35: ...en et service de votre appareil suite Figure 15 Forme des flammes du br leur ASSUREZ VOUS QUE LES FLAMMES SOIENT R GULI RES QU ELLES NE S L VENT P AS ET NE FLOTTENT P AS V rification du syst me d vacu...

Страница 36: ...the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Страница 37: ...re sur la pointe du thermocouple et l autre sonde sur le fil de cuivre du thermocouple Allumer la veilleuse et appuyer sur le bouton de la valve Si la tension est inf rieure 15 mV remplacer le thermoc...

Страница 38: ...debris or blockage 6 Glass soots a Flame impingement Adjust the log set so that the flame does not excessively impinge on it b Improper venturi setting Adjust the air shutter located on the control p...

Страница 39: ...izontal doit tre juste assez inclin e pour emp cher l eau de p n trer dans l appareil L inclinaison maximum est de 1 4 in vers le bas d Porte vitr e mal ferm e et fuites aux coins des joints d tanch i...

Страница 40: ...al accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installati...

Страница 41: ...aura cess de produire le mod le Les r glages l entretien normal le nettoyage et les r parations temporaires ne sont pas soumis au tarif de r paration et ne sont pas couverts par la garantie Le remplac...

Отзывы: