11
September 24, 2018
7080-165D
TREKKER FS
USA INSTALLATIONS:
A non-combustible floor protection is recommended
extending beneath the flue pipe when installed with
horizontal venting or under the Top Vent Adapter with
vertical installation.
CANADA INSTALLATIONS
:
A non-combustible floor protection extending beneath the
flue pipe is required with horizontal venting or under the
Top Vent Adapter with vertical installation.
Use a non-combustible floor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the glass
door.
32-1/8 in.
minimum
30-1/4 in.
minimum
6 in
(FROM FUEL DOOR
OPENING)
6 in
USA
6 in
FUEL DOOR OPENING
24-1/4 in.
minimum
152mm
from fuel door opening
816mm
minimum
768mm
minimum
CANADA
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
152mm
152mm
FUEL DOOR OPENING
514mm
minimum
44-1/8 in.
22-5/8 in.
24-1/4 in.
39-3/4 in.
USA
6 in.
from the fuel door
opening
1121mm
575mm
616mm
1010mm
152mm
(front door opening)
CANADA
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
Figure 11.1
Figure 11.2
Figure 11.3
Figure 11.4
C. Hearth Pad Requirements (UL & ULC)
Fire Risk
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
WARNING