background image

24

September 24, 2018

7080-165D

TREKKER FS

Mobile Home Installation

You must use a Quadra-Fire Outside Air Kit for 

installation in a mobile home.

1.  An outside air inlet must be provided for the 

combustion air and must remain clear of leaves, debris, 

ice and/or snow. It must be unrestricted while the 

appliance is in use to prevent room air starvation which 

causes smoke spillage. Smoke spillage can also set off 

smoke alarms.

2.  The combustion air duct system must be made of 

metal. It must permit zero clearance to combustible 

construction and prevent material from dropping into 

the inlet or into the area beneath the dwelling and 

contain a rodent screen.

3.  The appliance must be secured to the mobile home 

structure by bolting it to the floor (using lag bolts). 

Use the same holes that secured the appliance to the 

shipping pallet.

4.  The appliance must be grounded with #8 solid copper 

grounding wire or equivalent, terminated at each end 

with an NEC approved grounding device.

5.  Refer to Clearances to Combustibles and floor 

protection requirements on page 8 for listings to 

combustibles and appropriate chimney systems.

6.  Use silicone to create an effective vapor barrier at 

the location where the chimney or other component 

penetrates to the exterior of the structure.

7. 

Follow the chimney manufacturer’s instructions when 

installing the vent system for use in a mobile home.

8.  Installation shall be in accordance with the 

Manufacturers Home & Safety Standard (HUD) CFR 

3280, Part 24.

Part Number: OAK-3

Spark Arrestor Cap

Roof Flashing 

Storm Collar 

Joist Shield/Firestop 

Approved Class L 

or PL Pellet Vent

 

Figure 24.1

WARNING

Products of combustion generate carbon monoxide 

and different fuels generate different levels.  Carbon 

monoxide

• 

Only use approved fuels in this appliance.

• 

Always keep door shut during operation. Operating 

this appliance with doors open can allow CO to leak 

into the home.

CO can kill you before you are aware it is in your home. 

At lower levels of exposure, CO causes mild effects that 

are often mistaken for the flu. These symptoms include 

headaches, dizziness, disorientation, nausea and fatigue. 

The effects of CO exposure can vary greatly from person 

to person depending on age, overall health and the 

concentration and length of exposure.

WARNING

It is critical to have a working smoke detector 

installed in the home of appliance operation.

 

•  Smoke alarms that are properly installed and 

maintained play a vital role in reducing fire deaths 

and injuries. Having a working smoke alarm reduces 

the chance of fire related injuries..

CAUTION

Never draw outside combustion air from:

• 

Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

NEVER INSTALL IN A SLEEPING ROOM.

WARNING

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE 

HOME FLOOR, WALL AND CEILING/ROOF MUST BE 

MAINTAINED

Do NOT cut through:

• 

Floor joist, wall, studs or ceiling trusses.

• 

Any supporting material that would affect the 

structural integrity.

This appliance is to be connected to a factory-built 

chimney conforming to CAN/ULC-S629, Standard for 

650°C Factory-Built Chimneys.

For removal of the chimney for mobile home 

transportation, contact the proper transportation officials.

Содержание TREKKER-CSB

Страница 1: ...these instructions is not followed exactly a fire could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of th...

Страница 2: ...Venting Systems 17 A Through The Wall 17 B Vertical into Existing Class A Chimney 18 C Through The Wall Vertical Exterior 18 D Vertical Interior Typical Installation 18 E Masonry 19 F Alternate Mason...

Страница 3: ...bs Fuel Wood Pellets Weighted average LHV efficiency using data collected during EPA emissions test Weighted average HHV efficiency using data collected during EPA emissions test A range of BTU output...

Страница 4: ...f such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause birth d...

Страница 5: ...ent additional support to meet this weight requirement prior to installation The weight of the appliance is 426 lbs with a full load of fuel the max weight is 473 lbs NOTICE Check building codes prior...

Страница 6: ...t mount brackets will slide downwards from appliance Figure 6 2 4 Carefully pull appliance off of pallet and put in desired location following Hearth Pad and Clearance to Combustibles on pages 8 9 Too...

Страница 7: ...hecklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check outlet wi...

Страница 8: ...6 in 147mm 2 9 16 in 65mm 3 13 16 in 97mm 14 1 16 in 357mm Figure 8 2 Top View with Top Vent Adapter TPVNT 3 and Offset Adapter 811 0720 Figure 8 5 Top View with Top Vent Adapter TPVNT 6 and Offset Ad...

Страница 9: ...Adapter 812 3570 25 3 8 in 646mm 25 3 8 in 646mm 27 1 8 in 688mm 27 1 8 in 688mm Figure 9 4 Side View with Top Vent Adapter TPVNT 6 and Offset Adapter 811 0720 29 in 738mm 29 in 738mm 30 5 8 in 779mm...

Страница 10: ...ns and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Horizontal Through the Wall Inches Millimeters A Back...

Страница 11: ...ance M from the surface of the glass door 32 1 8 in minimum 30 1 4 in minimum 6 in FROM FUEL DOOR OPENING 6 in USA 6 in FUEL DOOR OPENING 24 1 4 in minimum 152mm from fuel door opening 816mm minimum 7...

Страница 12: ...eight 43 1092 n a n a B Width 40 1016 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and...

Страница 13: ...and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in tab...

Страница 14: ...iance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pe...

Страница 15: ...r Kit and the 3 to 6 inch 76 152mm Top Vent Offset Adapter are tested to use 24 gauge single wall flue connector or Listed double wall flue connector to Class A Listed metal chimneys or masonry chimne...

Страница 16: ...tude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe is required Figure 16 1 Ven...

Страница 17: ...ome installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage through a wall o...

Страница 18: ...Minimum Rain Cap Flashing 3 in 76mm Min 6 in 152mm Min 3 to 3 in 76 to 76mm Top Vent Kit Clean out Cover Figure 18 3 We recommend a minimum of 60 inches 1524mm vertical however above the eave is prefe...

Страница 19: ...mm clearance with firestop Figure 19 1 Figure 19 2 Concrete Cap Non combustible Hearth Pad 6 in 152mm Min Airtight clean out door Sheathing 1 in 25mm clearnance Flashing Fireclay Flue Liner with airsp...

Страница 20: ...ination Cap Wire Tie Trim Ring Wire Tie Collar 3 inch Aluminum Flex Pipe not included CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or gar...

Страница 21: ...e 21 2 4 Install the 5 mounting screws 3 on the left and 2 on the right 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the...

Страница 22: ...entations on the bottom to fit over the screw heads Log rests in front of screws Right Log Figure 22 3 Figure 22 4 E Optional Log Set Placement Instructions 2 PIECE LOG SET INSTALLATION 1 Place the le...

Страница 23: ...ects Away from drafts and direct heat from the appliance Mount base plate using screws and anchors provided using the level as a guide If necessary drill 3 16 holes for drywall or drill 7 32 for plast...

Страница 24: ...t Number OAK 3 Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 24 1 WARNING Products of combustion generate carbon monoxide and different...

Страница 25: ...25 September 24 2018 7080 165D TREKKER FS A Service and Maintenance Log 8 Reference Materials Date of Service Performed By Description of Service...

Страница 26: ...26 September 24 2018 7080 165D TREKKER FS Date of Service Performed By Description of Service...

Страница 27: ...r Hearth and Home Technologies does not sell directly to consumers Provide model number and serial number when requesting service parts from your dealer or distributor Stocked at Depot ITEM DESCRIPTIO...

Страница 28: ...te purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ De...

Отзывы: