Quadra-Fire  •  TOPAZ-MBK-IPI, TOPAZ-D-PMH-IPI, TOPAZ-D-MBK-IPI, TOPAZ-D-CSB-IPI Installation Manual •  2341-980_R10  •  11/15

48

A.  Fuel Conversion

•    Make sure the appliance is compatible with available gas 

types.

•  Conversions must be made by a qualified service 

technician using Hearth & Home Technologies specified 

and approved parts.

B.  Gas Pressure

•  Optimum appliance performance requires proper input 

pressures.

•    Gas line sizing requirements will be determined in ANSI 

Z223.1 National Fuel Gas Code in the USA and CAN/CGA 

B149 in Canada.

•    Pressure requirements are:

C.  Gas Connection

 •    Refer  to  Reference  Section  3  for  location  of  gas  line 

access in appliance.

•    Ensure that gas line does not come in contact with outer 

wrap of the appliance. Follow local codes.

•    Connect  incoming  gas  line  to  the  1/2  in.  (13  mm) 

connection on manual shutoff valve.

WARNING!  Risk of Fire or Explosion! 

Support control 

when attaching pipe to prevent bending gas line.

•    A small amount of air will be in the gas supply lines. 

WARNING! Risk of Fire or Explosion! 

Gas build-up during 

line purge could ignite. 
•  Purge should be performed by qualified service technician.
•  Ensure adequate ventilation. 
•  Ensure there are no ignition sources such as sparks or 

open flames.

Light the appliance. It will take a short time for air to purge 

from lines. When purging is complete the appliance will light 

and operate normally.

WARNING!  Risk of Fire, Explosion or Asphyxiation! 

Check  all  fittings  and  connections  with  a  non-corrosive 

commercially available leak-check solution. 

DO NOT

 use 

open flame. Fittings and connections could have loosened 

during shipping and handling.

WARNING! Risk of Fire! DO NOT

 change valve settings. 

This valve has been preset at the factory.

D.  High Altitude Installations

NOTICE: 

If the heating value of the gas has been reduced, 

these rules do not apply. Check with your local gas utility or 

authorities having jurisdiction.

When installing above 2000 feet  elevation:

•    In  the  USA:  Reduce  input  rate  4%  for  each  1000  feet  

above 2000 feet.

•   In  CANADA:  Input  ratings  are  certified  without  a 

reduction of input rate for elevations up to 4500 feet 

(1370 m)above sea level. Please consult provincial and/

or local authorities having jurisdiction for installations at 

elevations above 4500 feet (1370 m).                                   

Check with your local gas utility to determine proper orifice 

size.

WARNING! Risk of Fire or Explosion! 

High pressure will 

damage valve. Low pressure may cause explosion.

•    Verify inlet pressures. Verify minimum pressures when 

other household gas appliances are operating. 

•  Install regulator upstream of valve if line pressure is 

greater than 1/2 psig.

Gas Information 

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

10.0 in. w.c.

13.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

Note: 

Have the gas supply line installed in accordance with 

local  codes,  if  any.  If  not,  follow  ANSI  223.1.  Installation 

should  be  done  by  a  qualified  installer  approved  and/or 

licensed as required by the locality. (In the Commonwealth of 

Massachusetts installation must be performed by a licensed 

plumber or gas fitter).

Note: 

A listed (and Commonwealth of Massachusetts 

approved) 1/2 in. (13 mm) T-handle manual shut-off valve 

and flexible gas connector are connected to the 1/2 in. (13 

mm) control valve inlet. 

•   If substituting for these components, please consult 

local codes for compliance.

Fire Risk.
Explosion Hazard.
High pressure will damage valve.
•  Disconnect  gas  supply  piping  BEFORE 

pressure testing gas line at test pressures 

above 1/2 psig.

•  Close  the  manual  shutoff  valve  BEFORE 

pressure testing gas line at test pressures equal 

to or less than 1/2 psig.

WARNING

!

Содержание TOPAZ-MBK-IPI

Страница 1: ...gas fitter See Table of Contents for location of additional Commonwealth of Massachusetts requirements DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or an...

Страница 2: ...rmination Location and Vent Information A Vent Termination Minimum Clearances 9 B Chimney Diagram 10 C Approved Pipe 11 D Use of Elbows 12 E Measuring Standards 12 F Venting Guidelines for Horizontal...

Страница 3: ..._____ Electrical Section 8 Pg 44 47 Unswitched power 110 120 VAC provided for the appliance ___________________________ Switch wires properly installed ___________________________ Gas Section 9 Pg 48...

Страница 4: ...risdiction for installations at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size E Non Combustible Materials Specification Material which will not i...

Страница 5: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Note Th...

Страница 6: ...e dry B Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Hammer Phillips screwdrive...

Страница 7: ...r reference only Figure 3 1 Appliance Dimensions Location Inches Millimeter Location Inches Millimeter A 27 3 8 695 E 13 3 4 349 B 8 7 8 225 F 23 1 8 587 C 29 1 2 749 G 27 3 4 705 D 22 7 8 581 H 18 45...

Страница 8: ...TOPAZD CSB IPI Inches 6 1 2 3 5 1 2 66 1 4 36 40 36 3 4 3 1 Millimeters 165 76 127 25 51 1683 914 1016 933 76 25 C or C C or C G A A C Hearth Extension Floor Protection CAUTION Risk of Fire or Injury...

Страница 9: ...ENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NO...

Страница 10: ...HERE TERMINAL IS NOT PERMITTED O N P R Q Electrical Service V K V K V L C V QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QM...

Страница 11: ...CATED VENTING COMPONENTS This product is approved to be vented either horizontally through the side wall or vertically through the roof You may vent through a Class A or masonry chimney if an approved...

Страница 12: ...286 Figure 4 5 Vertical and Horizontal Offset for SLP Elbows Vent Type X Y Inches Millimeters Inches Millimeters SLP 5 127 11 3 4 298 SLP Pipe Effective Length Rise Run Inches Millimeters Inches Milli...

Страница 13: ...ust be installed When penetrating a combustible ceiling a ceiling firestop must be installed Top Vent Horizontal Termination Two 45 Elbows Installation requirements to replace the first 90 elbow with...

Страница 14: ...2 ft 610 mm 3 ft 914 mm 8 ft 2 4 m 4 ft 1 2 m 12 ft 3 7 m 6 ft 1 8 m 14 ft 8 in 4 5 m 8 ft 2 4m 17 ft 4 in 5 3 m 10 ft 3 0 m 20 ft 6 1 m 12 ft 3 7 m 18 ft 10 in 5 7 m 16 ft 4 9 m 16 ft 4 in 5 0 m 20...

Страница 15: ...Elbows INSTALLED HORIZONTALLY H1 H2 V1 Figure 4 9 2 Elbows to Max Horizontal V1 Minimum H1 H2 Maximum 3 ft 914 mm 5 ft 1 5 m 4 ft 1 2 m 9 ft 2 7 m 6 ft 1 8 m 11 ft 8 in 3 6 m 8 ft 2 4 m 14 ft 4 in 4 4...

Страница 16: ...VERTICALLY OR HORIZONTALLY Figure 4 10 Top Vent Horizontal Termination continued Three Elbows 3 Elbows to Max Horizontal V1 Minimum HTOTAL Maximum 3 ft 914 mm 2 ft 610 mm 4 ft 1 2 m 6 ft 1 8 m 6 ft 1...

Страница 17: ...IPI TOPAZ D MBK IPI TOPAZ D CSB IPI Installation Manual 2341 980_R10 11 15 17 Note As vertical pipe increases a flue restrictor may be required Top Vent Vertical Termination No Elbow Figure 4 11 V1 V...

Страница 18: ...ft 914 mm 34 ft 10 3 m 5 ft 1 5 m 4 ft 1 2 m 27 ft 9 in 8 5 m 9 ft 2 7 m 6 ft 1 8 m 23 ft 6 in 7 2 m 11 ft 8 in 3 6 m 8 ft 2 4 m 19 ft 3 in 5 9 m 14 ft 4 in 4 4 m 10 ft 3 1 m 15 ft 4 6 m 17 ft 5 2 m...

Страница 19: ...Max Horizontal V1 Minimum V1 V2 Maximum H1 H2 Maximum 3 ft 914 mm 38 ft 3 in 11 7 m 2 ft 610 mm 4 ft 1 2 m 32 ft 3 in 9 8 m 6 ft 1 8 m 6 ft 1 8 m 28 ft 3 in 8 6 m 8 ft 8 in 2 6 m 8 ft 2 4 m 24 ft 7 3...

Страница 20: ...4 ft 4 in 4 4 m 14 in 356 mm 10 ft 3 1 m 6 in 152 mm 17 ft 5 2 m 14 in 356 mm 12 ft 3 7 m 6 in 152 mm 15 ft 10 in 4 8 m 14 in 356 mm 16 ft 4 9 m 6 in 152 mm 13 ft 4 in 4 1 m 14 in 356 mm 20 ft 6 1 m 6...

Страница 21: ...6 in 152 mm 14 in 356 mm 11 ft 4 in 3 5 m 10 ft 3 1 m 6 in 152 mm 14 in 356 mm 14 ft 0 in 4 3 m 12 ft 3 7 m 6 in 152 mm 14 in 356 mm 12 ft 10 in 3 9 m 16 ft 4 9 m 6 in 152 mm 14 in 356 mm 10 ft 4 in 3...

Страница 22: ...Elbow Figure 4 16 H1 V1 H1 Minimum H1 Maximum V1 Minimum V1 Maximum 6 in 152 mm 14 in 356 mm 6 ft 1 8 m 40 ft 12 2 m Note As vertical pipe increases a flue restrictor may be required Note A derating o...

Страница 23: ...14 in 356 mm 11 ft 4 in 3 5 m 24 ft 7 3 m 10 ft 3 1 m 6 in 152 mm 14 in 356 mm 14 ft 4 3 m 19 ft 10 in 6 0 m 12 ft 3 7 m 6 in 152 mm 14 in 356 mm 12 ft 10 in 3 9 m 21 ft 9 in 6 6 m 16 ft 4 9 m 6 in 15...

Страница 24: ...through the ceiling support box until it protrudes approximately 3 in 76mm Connect the flex pipe to the retro connector and attach with sheet metal screws 6 Push the flex pipe back up into the ceiling...

Страница 25: ...aust Section Included in Chimney Liner Termination Kit 4 ft 1m of 3 in 76mm Flex Liner Air Intake Section Included in Chimney Liner Termination Kit The chimney must be sealed from the 4 ft 1m section...

Страница 26: ...to leave 2 3 in 51 76mm of flex above the existing chimney to allow for connection to the termination kit 5 Connect the flex liner to the top adapter using three sheet metal screws See Figure 4 19 6 F...

Страница 27: ...Included in Masonry Chimney Conversion Kit Wall Thimble Cover Included in Masonry Chimney Conversion Kit Figure 4 25 8 Secure the top adapter to the flashing Use three sheet metal screws through the s...

Страница 28: ...of Fire Coaxial to colinear venting configuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire CAUTION DO NOT use any flue restri...

Страница 29: ...Sides 1 in 25 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm If wall thickness is less than 4 in the existing heat shields must be field trimmed If wall thickness is greater than 7 1...

Страница 30: ...erior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be maintained See Section 7 F for information for regarding the installation of a horizontal termination cap Non Combustible W...

Страница 31: ...kept back from the pipe to prevent overheating D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insulation to touch vent Hearth Home Technologies requires the use o...

Страница 32: ...ent grille NG Orifice 33 LP Orifice 54 Tools Required Power drill 1 4 in hex driver bit 2 Phillips bit 3 8 in open end wrench high temperature sealant if required Note See appliance Installation Manua...

Страница 33: ...front glass assembly and take the glass assembly off the appliance See Figure 6 11 11 Remove the logs and refractory 12 The pilot needs to be lifted slightly to accommodate the burner removal Using 1...

Страница 34: ...all the pilot and the pilot shield to the burner 17 On inside of firebox remove plate and gasket on rear of firebox by removing three screws as shown in Figure 6 14 Discard gasket Replace screws on re...

Страница 35: ...Failure to maintain air space clearance may cause overheating and fire Figure 6 1 1 Thread Allen bolts through nuts until flush NOTE Two Allen bolts and two nuts are included in the component bag Norm...

Страница 36: ...securely fitted and locked into the preceding component Required Commercial Multi family Multi level exceeding two stories or High Rise Applications For installation into a commercial multi family mul...

Страница 37: ...Sections NOTICE If slip section is too long the inner and outer flues of the slip section can be cut to the desired length Apply a bead of silicone sealant 300 F minimum continuous exposure rating in...

Страница 38: ...upported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plum...

Страница 39: ...mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Cut the hole 1 8 in 3 mm l...

Страница 40: ...S MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Figure 7 11 Minimum Height From Roof To Lowest Discharge opening NOTICE Failure to properly caulk the roof flashing and pipe seams may...

Страница 41: ...de the assembled storm collar down the pipe section until it rests on the roof flashing see Figure 7 14 Tighten nut and make sure the collar is tight against the pipe section Caulk around the top of t...

Страница 42: ...A minimum 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1 4 in 184 mm The extended heat shield may need to be cut to length ma...

Страница 43: ...alling a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Bu...

Страница 44: ...pplicable electrical codes when it is installed in locations such as in bathrooms or near sinks Low voltage and 110 120 VAC voltage cannot be shared within the same wall box WARNING Risk of Shock Plug...

Страница 45: ...g the 6 volt transformer plug into the appliance junction box to supply power to the unit OR install 4AA cell batteries not included into the battery pack before use NOTICE Batteries should only be us...

Страница 46: ...und wire At the switch box connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction bo...

Страница 47: ...tely 45 degrees See Figure 8 3 It may be necessary to remove the on off switch wires from the zip tie that holds the gas line as well as from the wire clasp located on the side of the fan housing in o...

Страница 48: ...llations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction When installing above 2000 feet elevation...

Страница 49: ...stallation The air shutter is set fully open at the factory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 9 1 Loosen the wing nuts Slide the wing nut to the righ...

Страница 50: ...arrier 2 Remove front casting by lossening thumb screw at bottom of casting slide bottom of casting away from appliance 10 Appliance Setup B Remove the Shipping Materials Remove shipping materials fro...

Страница 51: ...refractory pieces are installed properly the gap between the refractory and the burner should be parallel See Figure 10 6 Figure 10 6 Place Left Side Refractory 4 Place the top refractory into the not...

Страница 52: ...or that type align the bracket with the appropriate set of screw holes and fasten it to the firebox with two screws Refer to Figure 10 9 and 10 10 LOG PLACEMENT INSTRUCTIONS Place rear log into applia...

Страница 53: ...on Ember material is shipped with this gas appliance To place the ember material Apply dime size pieces sparingly along front edge of burner Do not completely block ports Save the remaining ember mate...

Страница 54: ...1 2 in 165 mm 9 1 4 in 235 mm SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1...

Страница 55: ...The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is...

Страница 56: ...10 9 16 in 269 mm 14 in 356 mm 12 1 2 in 318 mm 12 in 305 mm SLP FLEX TRAP Horizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Supp...

Страница 57: ...mponents Diagrams continued SLP LPC SLP Low Profile Cap 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 17 7 8 IN 454...

Страница 58: ...n Manual 2341 980_R10 11 15 58 A Vent Components Diagrams continued DV 46DVA GCL Coaxial Colinear Appliance Connector LINK DV30B Flex Liner Kit 768 380A Stainless Steel Flex Pipe COAXIAL to COLINEAR V...

Страница 59: ...SLP48M 46 DVA 48 DL4 48 Pipe Length Black SLP48 BK 46 DVA 48B DL4B Adjustable Length 3 6 Black SLP6A B Adjustable Length 3 6 Galvanized SLP6AM Adjustable Length 3 7 Galvanized 46DVA 08A Adjustable Len...

Страница 60: ...P CCS BK 46DVA CS 4SS Ceiling Support 46DVA DC 4CS Co Axial to Co Lineal Appliance Connector 46DVA GCL CAA Decorative Ceiling Firestop Black SLP DCF BK 4TR Decorative Radius Cover DRC RADIUS Firestop...

Страница 61: ...Quadra Fire TOPAZ MBK IPI TOPAZ D PMH IPI TOPAZ D MBK IPI TOPAZ D CSB IPI Installation Manual 2341 980_R10 11 15 61...

Страница 62: ...ls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout featu...

Отзывы: