Quadra-Fire • SAPH-MBK-IPI, SAPH-D-PMH-IPI, SAPH-D-MBK-IPI, SAPH-D-CSB-IPI Installation Manual • 2343-980_R8 • 11/14
26
Existing Masonry Chimney
Prior to installing the gas stove, ensure that the existing chimney is functionally sound and clean.
• have the chimney and adjacent structure inspected and cleaned by qualified professionals. hearth & home
technologies recommends that NFI or CSIa certified professionals, or technicians under the direction of certified
professionals, conduct a minimum of a NFPa 211 level 2 inspection of the chimney.
• Replace component parts of the chimney and fireplaceas specified by the professionals.
Type C - Up & Out Installation
Type D - Hearth Mount
Figure 4.24
Type A & B Co-Axial to Co-Linear
Chimney Liner
Termination Cap
Co-Axial to
Co-Linear Connector
3 in. (76mm)
Flex Liner
Showing two
30 ft.
(9m)Sections
of Flex Liner
Chimney Liner
Termination Cap
Co-Axial to Co-Linear
Connector
30 ft. (9m) of 3 in.
(76mm) Flex Liner
Exhaust Section
4 ft. (1m) of 3 in. (76mm)
Flex Liner Air Intake Section
The chimney must be
sealed from the 4 ft. (1m)
section to termination
using a smoke shelf or a
flue restrictor. The seal
should be a minimum of
6 in. (152mm) below the
end of the 4 ft. (1m) Air
Intake section.
This section of the
chimney must be
sealed
TERMINATION
CAP
FLASHING
4 in. (102mm) FLEX
LINER
TOP ADAPTOR
RETRO
CONNECTOR
90° ELBOW
DIRECT
VENT PIPE
Chimney Liner
Termination Cap
30 ft. (9m) of 3 in. (76mm)
Flex Liner Exhaust Section
4 ft. (1m) of 3 in.
(76mm) Flex Liner
Air Intake Section
Chimney must be sealed
from 4 ft. (1m) section to
termination using a smoke
shelf or a flue restrictor.
Seal should be a
minimum of 6 in. (152mm)
below end of 4 ft. (1m) Air
Intake section.
This section of the
chimney must be sealed
Co-Axial to Co-Linear Connector
Alcove Clearance to
Combustibles must be
maintained. See Figure 3.2.
See COAXIAL/COLINEAR
Section and Figure 4.31.