background image

35

Troubleshooting

With proper installation, operation, and maintenance your gas fireplace will
provide years of trouble-free service.  If you do experience a problem, this
troubleshooting guide will assist a qualified service person in the diagnosis
of a problem and the corrective action to be taken. This troubleshooting
guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1.

 After repeated

triggering of the red

or black piezo button,

the spark ignitor will

not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode wire is

properly connected, replace the ignitor.

b. Defective pilot or
misaligned electrode

(spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or
black piezo button again. If the pilot lights, an improper gas/air mixture caused the
bad lighting and a longer purge period is recommended. If the pilot will not light,

ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a
strong spark. If the gap is OK, replace the pilot.

c. No gas or low gas

pressure.

Check the remote shut-off valvess from the fireplace. Usually, there is a valve near

the gas main. There can be more than one (1) valve between the fireplace and the

main.

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.

  The pilot will not

stay lit after carefully

following the lighting

instructions.

a. Defective

thermocouple.

Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the

pilot for maximum flame impingement.

Ensure that the thermocouple connection at the gas valve is fully inserted and tight

(hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt meter lead wire on

the tip of the thermcouple and the other meter lead wire on the thermocouple

copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less

than 15mV, replace the thermocouple.

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

3.

 The pilot is

burning, there is no

gas burner, the valve

knob is in the ON
position, and the

ON/OFF switch is in

the ON position.

a. ON/OFF switch or
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the jumper
wires across the terminals at the switch. If the burner comes on, replace the
defective switch. If the switch is OK, place the jumper wires across the switch wires
at the gas valve. If the burner comes on, the wires are faulty or connections are

bad.

b. Thermopile may
not be generating

sufficient millivoltage.

If the pilot flame is not close enough physically to the thermopile, adjust the pilot

flame.

Be sure the wire connections from the thermopile at the gas valve terminals are

tight and that the thermopile is fully inserted into the pilot bracket.

Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP

terminals of the gas valve. The meter should read 325 millivolts minimum, while

holding the valve knob depressed in the pilot position, with the pilot lit, and the

ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is

below the specified minimum.

With the pilot in the ON position, disconnect the thermopile leads from the valve.
Take a reading at the thermopile leads. The reading should be 325 millivolts

minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON

position. Check the millivolt meter a the thermopile terminals. The millivolt meter

should read greater than 125mV. If the reading is acceptable, and if the burner
does not come on, replace the gas valve.

d. Plugged burner
orifice.

Check the burner orifice for stoppage. Remove stoppage.

e. Wall switch or
wires are defective.

Follow the corrective action in Symptom and Possible Cause 1.a above. Check

the switch and wiring. Replace where defective.

Содержание QV-ST

Страница 1: ...FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...onents 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 27 Step 5 The Gas Control Systems 28 Step 6 The Gas Supply Line 28 Step 7 Gas Pressure Requirements 28 Step 8 Wir...

Страница 4: ...LP Exploded Parts Diagram Vue clat e des pi ces Part number list on following page La liste des num ros de pi ce se trouve la page suivante Service Parts 1 2 3 4 10 6 7 9 8 6 7 9 8 12 11 5 Log Set As...

Страница 5: ...S Orifice de br leur GN 32DMS 573 800 Burner Orifice LP 1 8mm Orifice de br leur PL 1 8mm 501 801 Junction Box Bo tier de d rivation 100 250A Piezo Ignitor Allumage Pi zo 291 513 Thermopile Thermopile...

Страница 6: ...LP Exploded Parts Diagram Vue clat e des pi ces Part number list on following page La liste des num ros de pi ce se trouve la page suivante Service Parts 6 7 9 8 6 7 9 8 1 2 3 4 10 11 11 5 Log Set As...

Страница 7: ...3 800 Burner Orifice LP 1 8mm Orifice de br leur PL 1 8mm 501 801 Junction Box Bo tier de d rivation 100 250A Piezo Ignitor Allumage Pi zo 291 513 Thermopile Thermopile 060 512 Thermocouple Thermocoup...

Страница 8: ...odes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedro...

Страница 9: ...instructions will void the own er s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Hearth Home Technologies disclaims any responsibility for the following actio...

Страница 10: ...LLE SIDE GLASS DOOR END GLASS DOOR TOP STANDOFFS TOP GRILLE TOP VENT COLLARS FRONT RIGHT SIDE LEFT SIDE 13 331mm 24 1 4 616mm 12 1 8 308mm VENT COLLARS 42 3 4 1086mm 28 7 8 735mm ELECTRICAL ACCESS 2 1...

Страница 11: ...RICAL ACCESS GAS LINE ACCESS GAS CONTROLS LABELS BOTTOM GRILLE TOP GRILLE TOP STANDOFFS GLASS DOOR 45 1143mm 13 330mm 12 1 8 308mm VENT COLLARS 24 1 4 616mm 28 7 8 733mm 2 1 2 64mm GAS LINE ACCESS 4 1...

Страница 12: ...t before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace facing material The dia gram below shows framing reference dimensions CAUTION...

Страница 13: ...4 41 1 2 23 1 4 45 29 7 8 QV PIER 43 1 4 44 41 1 2 23 1 4 45 29 7 8 Figure 4 Framing Dimensions NOTE DIMENSIONSSHOWNININCHES Shows center of 12 x 12 vent framing holes for top and rear venting The ce...

Страница 14: ...inch inner pipe 8 5 8 inch outer pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 15: ...nd the venting configuration used Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to...

Страница 16: ...16 Figure 7 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M STRAIGHT OUT HORIZONTAL VENTING H Max Run 24 610 mm Figure 8 Straight Out Horizontal Venting H V CAP...

Страница 17: ...2 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 86m 17 MAX 5 1m H 17 MAX 5 1m V H 37 MAX 11 3m Figure 10 Venting with One 90 Elbow V H 1 MIN 305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m...

Страница 18: ...MIN 1 22m 12 MAX 3 6m 5 MIN 1 5m 15 MAX 4 5m 6 MIN 1 86m 17 MAX 5 1m 17 MAX 5 1m V H 37 MAX 11 3m Figure 11 Venting with Two 90 Elbows VENTING WITH TWO 2 90 ELBOWS V FT H FT 1 MIN 305mm 3 MAX 914m 2 M...

Страница 19: ...X 2 7 m 4 MIN 1 22 m 8 MAX 2 48 m 12 MAX 3 6 m 8 MAX 2 48 m 17 MAX 5 1 m V H H1 37 MAX 11 3m Figure 12 Venting with Two 90 Elbows Figure 13 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V F...

Страница 20: ...m 4 MIN 1 22 m 8 MAX 2 48 m 15 MAX 4 5 m 8 MAX 2 48 m 17 MAX 5 1 m V H H1 H2 37 MAX 11 3m VENTING WITH THREE 3 90 ELBOWS V H H H1 H2 1 MIN 305 mm 2 MAX 610 mm 3 MAX 914mm 2 MIN 610 mm 4 MAX 1 22 m 6 M...

Страница 21: ...MIN 1 22m 12 MAX 3 6m 17 MAX 5 1m NOTE H H1 17 MAX 5 1m V V1 H H1 37 MAX 11 3m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 1 MIN 305mm 3 MAX 914m 2 MIN 610mm 6 MAX 1 86m 3 MIN 914mm 9 MAX 2 7m 4 MIN...

Страница 22: ...16 Follow the vent configuration tables accordingly Remove the insulation from the REAR five inch flue pull the heat shield out from outside of the firebox WARNING THE TOP HEAT SHIELD INSIDE THE FIREB...

Страница 23: ...e firestops Figure 20 12 x 12 Hole and Vent Pipe Figure 21 Heat Shield Interior Exterior Firestops VENT PIPE 1 25 4 mm 12 305mm 12 305mm TRIM HEAT SHIELD IF TOO LONG ADD TO SHIELD IF TOO SHORT EXTERIO...

Страница 24: ...iling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 23 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an att...

Страница 25: ...ermination cap to its final exterior position on the building WARNING THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP For trapezoidal cap termination kits Using screws secure t...

Страница 26: ...ne side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes...

Страница 27: ...of the building Roof Pitch H min ft flat to 6 12 1 0 6 12 to 7 12 1 25 over 7 12 to 8 12 1 5 over 8 12 to 9 12 2 0 over 9 12 to 10 12 2 5 over 10 12 to 11 12 3 25 over 11 12 to 12 12 4 0 over 12 12 t...

Страница 28: ...he shut off valve When attaching the pipe support the control so that the lines are not bent or torn Step 7 Gas Pressure Requirements Pressure requirements for Hearth Home Technolo gies gas fireplaces...

Страница 29: ...anently installed Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF s...

Страница 30: ...D A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE P...

Страница 31: ...lace dime size pieces of ember material about 1 2 inch apart near port holes in burner top Do NOT press em bers into burner ports Cover the top of the burner with a single layer of ember material For...

Страница 32: ...the control in the PILOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every sec...

Страница 33: ...in the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operat...

Страница 34: ...ntrol compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check o...

Страница 35: ...he pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Страница 36: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Страница 37: ...accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation...

Отзывы: