background image

12

05/22

8106-803B

B. Avoiding Smoke and Odors

Negative  Pressure,  Shut-Down  and  Electrical 

Power Failure

To  reduce  the  probability  of  back-drafting  or  burn-back 

in the pellet appliance during power failure or shut down 

conditions, it must be able to draft naturally without exhaust 

blower operation.
Negative pressure in the house will resist this natural draft if 

not accounted for in the pellet appliance installation.
Heat rises in the house and leaks out at upper levels. This 

air must be replaced with cold air from outdoors which flows 

into lower levels of the house.
Vents and chimneys into basements and lower levels of the 

house can become the conduit for air supply and reverse 

under these conditions.

Outside Air

An outside air kit is recommended in all installations. The 

Outside Air Kit must be ordered separately.

Per national building codes, consideration must be given to 

combustion air supply to all combustion appliances. Failure 

to supply adequate combustion air for all appliance demands 

may lead to back-drafting of those and other appliances.

When the appliance is roof vented (strongly recommended):

The air intake is best located on the exterior wall 

oriented towards the prevailing wind direction during 

the heating season.

When the appliance is side-wall vented:

The air intake is best located on the same exterior wall 

as the exhaust vent outlet and located lower on the wall 

than the exhaust vent outlet.

The outside air supply kit can supply most of the demands 

of the pellet appliance, but consideration must be given to 

the total house demand.
House demand may consume the air needed for the 

appliance. It may be necessary to add additional ventilation 

to the space in which the pellet appliance is located.
Consult with your local HVAC professional to determine the 

ventilation demands for your house.

Hearth & Home Technologies assumes no responsibility 

for, not does the warranty extend to, smoke damage 

caused by reverse drafting of pellet appliances under 

shut down or power failure conditions. 

Vent Configurations

When installing a pellet appliance with a horizontal vent 

configuration  the  frequency  of  power  outages  should 

be considered:
•  Power outages during operation will cause the appliance 

to immediately turn off and may create conditions where 

smoke will back draft into the house. In order to reduce 

the likelihood of smoke back drafting into the house 

during a power outage, Hearth and Home Technologies 

strongly suggests:

-  Installing the pellet venting with a minimum vertical 

run of 5 feet (1.52m).

-  Installing  the  outside  air  kit  at  least  4  feet  (1.22m) 

below the vent termination.

To prevent soot damage to exterior walls of the house and 

to prevent re-entry of soot or ash into the house:
•  Maintain specified clearances to windows, doors and air 

inlets, including air conditioners.

•  Vents should not be placed below ventilated soffits. Run 

the vent above the roof.

•  Avoid venting into alcove locations.
•  Vents should not terminate under overhangs, decks or 

onto covered porches.

•  Maintain minimum clearance of 12 inches (305mm) from 

the vent termination to the exterior wall. If you see deposits 

developing on the wall, you may need to extend this 

distance to accommodate your installation conditions.

• 

DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVICING ANOTHER APPLIANCE.

• 

DO  NOT  CONNECT  TO  ANY  AIR  DISTRIBUTION 

DUCT OR SYSTEM.

CAUTION

Содержание OUTFITTER-I

Страница 1: ...iquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING Hot glass will cause burns Do not touch glass...

Страница 2: ...Getting Started A Design Installation Location Considerations 5 B Thermostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Removal of Appliance from Pallet 6 F Install Checklist 7 3 Dimensions and Clearances A Appliance Dimensions 8 B Clearances to Combustibles UL and ULC 9 C Hearth Pad Requirements UL and ULC 9 4 Vent Information A Venting Terminatio...

Страница 3: ...HHV Tested Efficiency 74 6 EPA BTU Output 6 800 26 000 per hr BTU Input 9 600 to 33 200 per hr Vent Size 3 or 4 Type L or PL Hopper Capacity 60 lbs Fuel Premium Wood Pellets Weighted average LHV Low Heating Value efficiency using data collected during EPA emissions tests in accordance with the requirements of CSA B415 1 Weighted average HHV High Heating Value efficiency using data collected during...

Страница 4: ...Stove Composition These pellet burning stoves are made of steel cast iron or a combination of both with a ceramic viewing glass These stoves incorporate a self feeding system including a fuel storage hopper and a mechanical feed system which is controlled by a micro processing control board Each model contains a variable speed distribution blower to circulate room air through the heat exchanger an...

Страница 5: ...Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation on paper using exact measurements for clearances and floor protection before actually beginning the installation Lo...

Страница 6: ...Plated surfaces have been wiped clean with a soft cloth if applicable Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements Risk of Fire Damaged parts could impair safe operation Do NOT install damaged incomplete...

Страница 7: ...ing this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appliance Check outlet with multi meter for proper polarity and voltage 115 120 VAC Record voltage reading _____________ ATTENTION INSTALLER Follow this Standard Work Checklist This standard work checklist is to be ...

Страница 8: ...06 803B A Appliance Dimensions Figure 8 1 Top View 3 1 2 89mm Figure 8 3 Front View 21 3 4 552mm 33 3 4 858mm 7 7 8 200mm 11 3 8 289mm Figure 8 2 Side View 12 7 8 326mm 22 1 8 562mm 3 3 Dimensions and Clearances ...

Страница 9: ...hru 10 4 USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor protection extending beneath the flue pipe is required with horizontal venting or under the Top Vent Adapter with vertical installation D B A Figure 9...

Страница 10: ... 42 1067mm 13 58 346mm 24 7 8 632mm USA Figure 10 3 876mm 76mm 1067mm 346mm 632mm Canada Figure 10 4 Fire Risk Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING from side of appliance 2 51mm 25 635mm 28 7 8 733mm 13 5 8 346mm from front of appliance 6 152mm USA Figure 10 1 ...

Страница 11: ...P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table below 24 in Above grass top of plants wood or any other combus tible 12 in 36 in no OAK Clearance from any forced air intake of other appliance 12 in Clearance horizontally from combustible wall 15 in Vented directly through a wall mini...

Страница 12: ...demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house Hearth Home Technologies assumes no responsibility for not does the warranty extend to smoke damage caused by reverse drafting of pellet appliances un...

Страница 13: ... Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successful draft include Preventing negative pressure Location of appliance and chimney NOTE Follow venting manufacturers recommendations for sealing pipe joints E Minimum Vacuum Requirements 075 inches W C F Chimney and Exhaus...

Страница 14: ...left side of the chart 2 Move to the right horizontally on the chart until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe is required Pellet Venting Component of Elbows Feet of Pipe Multiplied By Equivalent Feet Components Equivalent Feet 90 Elbow or Tee ...

Страница 15: ...ere passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 Figure 15 1 Straight Out 6 152mm Minimum Non combustible Hearth Pad Wall Thimble Horizontal Termination Cap 2 51mm Minimum 6 152mm Minimum from glass NOTICE Please note that while the minimum clearance for the termination cap is 6 inches 152mm there is the possibility of so...

Страница 16: ... from 3 inch 76mm air clearance to no less than 1 inch 25mm air clearance to combustibles for approved Listed pellet pipe Follow pipe manufactures listed air clearances to combustibles and installation instructions for all reduced air clearances installations D Vertical into Existing Class A Chimney C Through The Wall Vertical External Horizontal B Vertical Interior Typical Installation Firestop F...

Страница 17: ...ner with Airspace Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Fire Risk Inspection of Chimney Masonry chimney must be in good condition Meets minimum standard of NFPA 211 Factory built chimney must be minimum 6 inch 152mm UL103 HT Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual prov...

Страница 18: ...tion cap is 6 inches 152mm there is the possibly of soot build up around the termination area If this occurs we suggest to move the termination further away from the house to prevent it The suggested minimum is 12 inches 6 in 152mm Minimum Non combustible Hearth Pad Wall Thimble Horizontal Termination Cap 2 in 50 8mm Minimum 6 in 152mm Minimum From Glass Straight Out Wall Thimble Illustration show...

Страница 19: ...ipe and run pipe through wall 5 Attach flex pipe to outside termination cap with second hose clamp 6 Secure termination cap to outside surface 7 Secure trim ring to interior wall A Outside Air Kit Kit 811 0872 uses a 2 inch flex hose which is included in the kit and uses hose clamps to secure the hose Parts Included in 2 inch Kit 811 0872 1 piece of 2 inch x 3 ft flex hose 2 hose clamps 1 collar a...

Страница 20: ...s direct sunlight above a lamp television radiator a wall next to a window or direct heat from the appliance Avoid damp environments as this can lead to corrosion that may shorten thermostat life If painting or construction work around cover the thermostat completely or wait until work is complete before installation 1 Connect your thermostat wire to the W and R terminals Figure 20 1 Figure 20 1 W...

Страница 21: ...m Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 7 7 Mobile Home Installation Products of combustion generate carbon monoxide and different fuels generate different levels Carbon monoxide Only use approved fuels in this appliance Always keep door shut during operation Operating this appliance with doors open can allow CO to leak into the home CO can kill you before you are awa...

Страница 22: ...22 05 22 8106 803B A Service Maintenance Log Date of Service Performed By Description of Service 8 8 Reference Materials ...

Страница 23: ... maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We recommend that you record the following pertinent information for your heating appliance Date purchased installed Serial Number Location on appliance Dealership purchased from Dealer Phone 1 Notes Th...

Отзывы: