The states shown in the table are:
State
displayed
Explanation
RUN
Good Status - Run Mode
PROG
Good Status - Prog Mode
*TOUT
Timeout - not being scanned (may be configuration mismatch)
*RST*
Scanner sending reset (may be configuration mismatch)
---
Empty Rack Location
If
Auto Refresh
is on, the display refreshes once a second.
You can refresh the screen at any time by clicking
Refresh
.
If values change, they are shown with a light green background for one display update after they have
changed. The first time you open the window, all values are regarded as new and are displayed with a
green background.
Click on any rack or partial rack to select it in the diagnostic counters table. If Auto Refresh is on,
you may have to click several times if the screen is being updated when you click.
Diagnostic Counters for the Selected Rack
This table shows the counters for the currently selected rack. The rack number and starting I/O group
are shown in the table heading.
The counters increment for discrete input and output packets, and do not include block transfer
packets.
The counters displayed are:
Counter
Description
Rx Good
Count of received good packets from this rack
Crc Err
Count of CRC errors for this rack
Tout Err
Count of timeout errors for this rack