AN-X4-ABRIO-SCAN Page
13
Installation
Prevent Electrostatic Discharge
The module is sensitive to electrostatic discharge.
WARNING!
Electrostatic discharge can damage integrated circuits and semiconductors.
Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential
•
Do not touch the connector pins
Power
AN-X requires DC power input of anywhere from 12 to 24 VDC
The pins on the power connector are chassis ground, negative voltage and positive voltage. Pin 1 is
closest to the Ethernet connector.
Power consumption is 240 mA @ 12VDC or 120 mA @ 24VDC.
The part number for the power connector is Phoenix MSTB 2.5/3-ST-5.08 (1757022)
The power connector is the same as the AN-X2 but is rotated 180 degrees.
Remote I/O Cabling and Termination
Follow Allen-Bradley cabling recommendations for remote I/O. Refer to
Approved Vendor List for
DH, DH+, DH-485, and Remote I/O Cables
, publication ICCG-2.2, February 1996.
The network cable must be terminated with terminating resistors attached to the physical ends of the
network, usually 82 ohm, but refer to Allen-Bradley documentation since some devices require 150
ohm terminators. There should be two and only two terminators on the remote I/O network.