On the AN-X module, the remote I/O connections should be as shown. The wiring in the connector is
that same as for the AN-X2 but the connector is rotated 180 degrees on the AN-X4. A remote I/O
cable for the AN-X2 can be used without change on the AN-X4.
Line 2 on the AN-X is closest to the Ethernet connector and the NS LED.
Check the wiring to ensure that line 1 on the AN-X is connected to line 1 on the PLCs, and other
devices.
The part number for the connector is Phoenix MSTB 2.5/3-ST-5.08 (1757022)
The most common causes of remote I/O connection errors are:
•
wiring reversed (lines 1 and 2)
•
incorrect baud rate
•
other cabling and termination problems
•
terminating resistors shorted to shield wires
•
duplicate racks
Usually, but not always, the wire colors are:
Data Highway Plus
Remote I/O
Line 1
Clear
Blue
Line 2
Blue
Clear
Ethernet Cabling
AN-X has a standard RJ-45 connector for connecting to Ethernet.
If you are connecting AN-X to an existing network through a router or switch, use a standard Ethernet
cable.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D hazardous locations
or non-hazardous locations.
Device is to be mounted inside an environmentally suitable enclosure that requires a tool to access.
Device is for indoor use only.