Atmospheric Oil Mist Detection System
TM4 / AUGUST 2018
EMAIL [email protected] WEBSITE www.oilmist.com 4 East Barnet Road, London, England, EN4 8RW TEL +44 (0)20 7328 3121
Sheet-33
QMI TRIPLEX 4-20MA ANALOGUE DATA OUTPUT
(OPTIONAL)
Location of Data Logger PCB
Close up of Data Logger PCB
The data collected can be used to determine the cause of a build-up towards a possible
explosion and help find a solution.
The Monitor sends out a 4-20mA signal corresponding to the displayed mist percentage
for each Sensor. This is a digitally calculated reading taking into account temperature
non-linearities of the Sensors and oil deposit build-ups within the Sensor.
The signal can be recorded using a chart recorder, or data logger and corresponds to
the reading shown in the display.
Current = (Display % x 16 ÷156) + 4
Display
0
10
20
30
40
50
60
70
80
90
mA
4.00
5.00
6.00
7.10
8.10
9.10
10.20 11.20 12.20 13.20
Display
100
110
120
130
140
150
160
170
180
mA
14.30 15.30 16.30 17.30 18.40 19.40 20.41 21.40 22.50
The 4-20mA output from the Monitor is available on the 5-way connector, bottom
right of the Monitor as shown in the location of the data logger PCB image above.
Data Logger Harting Plug PIN Out
Harting PIN
Channel / Voltage
1
1/0
2
2/0
3
3/0
4
12+Volts
5
No connection should be made to this terminal
Cable must be 4 core with a diameter of 0.5 mm
2
.