Atmospheric Oil Mist Detection System
TM4 / AUGUST 2018
EMAIL [email protected] WEBSITE www.oilmist.com 4 East Barnet Road, London, England, EN4 8RW TEL +44 (0)20 7328 3121
Sheet-35
To check alarm level setting
1. Place the magnetic pen over the circle marked ALARM LEVEL, the alarm level indicator
will illuminate.
2. Place the magnetic pen over the CHANNEL number and the channel identification display
will show digitally the value of the mist density.
To change alarm level setting
NOTE:
During the setting procedure, normal Monitor functions are disabled.
1. Fit and turn the Security Key clockwise ¼ turn, the light above CHECK ALARM
SETTINGS will illuminate.
2. Place the magnetic pen on the circle marked CHECK ALARM SETTINGS.
3. Place the magnetic pen on the circle marked RAISE ALARM SETTING
(‘+’ RAISE or ‘-‘ LOWER) lift the magnetic pen and replace to change the level by 1
increment. Continue until the required setting is achieved. The level will be shown on the
digital display.
4. Place the magnetic pen on the selected circle CHANNEL NUMBER to set that channel to
the level selected.
5. The setting is complete, turn the Security Key ¼ turn anti-clockwise, (to lock the
system) and remove the key.
CHANGING THE DIGITAL DISPLAY USING THE MAGNETIC PEN (Q0109)
Oil mist level reading, setting,
and fault location readout
Channel
identification
ALARM LEVEL, CHECKING AND CHANGING