3. FAULT ALARMS
The fault alarms indicate if there is any fault in the monitoring system. The Monitor
faceplate has a list of the fault alarms and their significance. This uses relay RL8. See
table below for the fault conditions as presented on the Monitor faceplate. For more
information see the fault directory - Sheet-41 - Sheet-42.
Channel
Reading
Response
1 - 3
F1
Check & repair relevant cable
1 - 3
F2
Clean Sensor according to instructions
using an
Isopropyl Alcohol
1 - 3
F3
Clean Sensor
Check Sensor fan
Replace Sensor
See Fault Directory Sheet-41 of Manual
C
IC
Check operating instructions
If ‘No CPU’ light is on, there is a processor fault.
‘dd’ on test indicates when the Sensor is dirty so it is necessary to clean the lens.
‘cd’ on test indicates when the Sensor is clean.