When the maximum cell or rack voltage is
above protection level, thus terminating the
system. Automatically returns to normal
when the maximum cell or rack voltage goes
below the limit value.
BAT1 Cell or Rack
Over Voltage Protection
BAT1 CEL OV
P
B04P
When the minimum cell or rack voltage is
below protection level, thus terminating the
system. Automatically returns to normal
when the minimum cell or rack voltage goes
above the limit value.
BAT1 Cell or Rack
Under Voltage
Protection
BAT1 CEL UV
P
B05P
When the maximum cell temperature is
above protection level, thus terminating the
system. Automatically returns to normal
when the maximum cell temperature goes
below the limit value.
BAT1 Cell Over Temp
Protection
BAT1 CEL OT
P
B06P
9.1.2 Battery General Events (Protection)
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BAT1 Charge Over
Current Protection
BAT1 CHG
OC P
B01P
WEB Display
HMI Display
Description
Measures
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BAT1 Discharge Over
Current Protection
BAT1 DCHG
OC P
B02P
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
BAT1 Cell Voltage
Sensing Data Hold
Protection
BAT1 CEL V
HOLD P
B03P
Type : PROTECTION
93
I
Problem Confirmation