Electrical Connections
Type
Grid
Strip Length
5.8.3 Battery Connection Method
To connect the Battery, you need 3 connections :
Ground, (+) and (-). In any case, connection of the INVERTER to ground is mandatory.
To connect the Battery, insert the cable into the INVERTER through the Battery cable gland.
Strip 9 mm of cable from the cable to connect to Load. Connect the Battery cable to the Filter Board CN401.
After lifting the handle of connector, insert the cable and lower the handle of the connector to secure the
Battery cable. Be sure to use the correct size cable and be free from flicker.
5.8.4 Feature and Size of Cable
The following lists the insulation strip length details for each conductor cross section.
Refer to Chapter 5.1.2 for cable specification. The ground wire should be grounded by crimping the ring
terminal. Refer to Chapter 2.3.4 for work on ring terminal.
[ Figure 5-21 : Power Cable Connection to the Load Connector ]
[ Table 5-8 : Insulation Strip Lengths ]
PE
L
N
L
N
L = N = 210 mm
7-8 mm
PE = 120 mm
//
//
9 mm
9 mm
9 mm
9 mm
9 mm
9 mm
PE
L = N = 230 mm
7-8 mm
PE = 115 mm
//
//
PE
L = N = 170 mm
7-8 mm
PE = 150 mm
//
//
Load
Battery