Exhaust Requirements
Machine
Exhaust
Requirement
Machine Duct Size
Air Velocity at Test
Point (ft/min)
Air Velocity at
Test Point (m/sec)
DeltaTherm 4’
200 CFM
4” (102mm)
2292
11.6
DeltaTherm 8’
300 CFM
6” (152mm)
1528
7.8
DeltaTherm 8’ H
140 CFM
6” (152mm)
713
3.6
DeltaTherm 12’
600 CFM
6” (152mm)
3056
15.5
DeltaTherm 12’ H
210 CFM
6” (152mm)
1070
5.4
DeltaTherm 16’
1000 CFM
6” (152mm)
5093
25.9
DeltaTherm 16’ H
280 CFM
6”
(152mm)
1426
7.2
194B193B193B
Note:
Check machine specifications. Custom order machines and processes may require
higher exhaust flow rates.
Air Velocity Test Point
195B194B194B
Measure the velocity at the inlet to the factory supplied duct.
196B195B195B
3B3B3B
Figure 4: Air Velocity Test Point