PureAire Monitoring Systems, Inc.
2/22/2000
8
3.1.3 Model TX-KP
(Explosion-Proof)
The transmission cable should be connected to terminal block CN3 in the
explosion-proof housing. The white (+) wire connects to terminal #1, the black
(-) to terminal #2, and shield (S) to terminal #3.
IMPORTANT:
Do not switch the polarity of the 24 VDC power line. The white
(+24 VDC) line must connect to terminal #1 and the black (0 VDC) power line
must connect to terminal #2.
TX-KP
Bionics Instrument Co., Ltd.
GAS DE TECTOR
CN1
CN3
1 2 3 4
LOAD
GND
DC 24V Power Supply
C
M
A
+
Shield
Shield
-
+
PC-1280RU
Transmission
Cable Inlet
NPT 3/4"
Transmission
Cable
3
2
1
Shield
+(White)
-(Black)
+(White)
- (Black)
TX-KP Transmission Cable Wiring