Troubleshooting 

 

Too Much Humidity 

 

 

 

1.  Humidity controller out of calibration. 

 

2.  Valve stem sticking. 

 

3.  Valve spring broken. 

 

4.  Foreign matter preventing valve from closing. 

 

Too Little Humidity 

 

 

1.  Strainer screen plugged. 

 

2.  Stop valve not fully open. 

 

3.  Humidity controller out of calibration. 

 

4.  Inadequate steam pressure. 

 

5.  Undersized humidifier. 

 

6.  Automatic control valve not opening fully. 

 

 

A)  Pneumatic valve operator leaking air. 

 

 

B)  Valve stem sticking. 

 

Humidifier Discharges Water 

 

  

1.  Faulty drainage: 

 

 

A)  Return line pressure greater than humidifier pressure. 

 

 

B)  Return line flooded. 

 

 

C)  Dirty steam trap. 

 

 

D)  Vertical lift. 

 

 

E)  Wrong type steam trap, float type must be used. 

 

 

F)  Tube assembly not level. 

 

 

2.  Faulty steam supply: 

 

 

A)  Humidifier supply not taken from top of main. 

 

 

B)  Long, un-trapped supply line. 

 

 

C)  Steam main flooded due to priming boiler. 

 

 

 

Содержание INSTY-PAC

Страница 1: ...gravity to an open drain condensate cannot be elevated 4 Each condensate connection must have it s own steam trap Condensate connections cannot be combined together to a common steam trap 5 A common...

Страница 2: ...cking CSCC and chloride pitting of stainless steel components is not covered by warranty Do not use hydrochloric acid descalers or bleach to clean the tank Consult the factory if you are unsure about...

Страница 3: ...70 80 85 Relative Humidity Leaving Relative Humidity Leaving Relative Humidity Entering Relative Humidity Entering Non Wetting Distance With a Insty Pac Tube Assembly Having 6 Centers The above is ba...

Страница 4: ...wall for the supply connection If the alternate horizontal condensate drain connection is supplied cut a 1 1 16 diameter hole through the AHU or duct wall for the drain connection see Fig 3 3 Install...

Страница 5: ...supply inlet 5 Duct plate condensate 1 6 Tube support bracket 1 per tube bank 7 Flexible connector 1 per tube 1 NPT valve connection 4 2 6 3 Fig 2 Tube drain connection 3 4 NPT Header drain connection...

Страница 6: ...g bracket welded to header Notes 1 Center the multiple injection tube assembly in the duct height 2 The injection tubes should be mounted level within the duct or AHU 3 Install injection tubes with th...

Страница 7: ...g VAV high limit humidistat is required A minimum velocity of 300 feet per minute is required to avoid saturation and excessive fog travel Controls Fan Interlock Switch PURE Humidifier Co recommends t...

Страница 8: ...ure 5 Undersized humidifier 6 Automatic control valve not opening fully A Pneumatic valve operator leaking air B Valve stem sticking Humidifier Discharges Water 1 Faulty drainage A Return line pressur...

Страница 9: ...is not leaking air b the valve closes off tightly c the stem packing is not leaking steam Valve Electric Should be inspected annually to confirm that the stem packing is not leaking and that the valv...

Страница 10: ...9...

Страница 11: ...10...

Страница 12: ...11 141 Jonathan Blvd North Chaska MN 55318 Tel 952 368 9335 Fax 952 368 9338 www purehumidifier com...

Отзывы: