3.5 Technical data and functions of the intelligent electric pump
NOTE:
The pump will be in the ON position when touching water and in the OFF position when emerging
from the water.
Intelligent water level control mode on the electric pump
•
When the pump and the float switch (or water level sensor) is "ON", the pump will start.
•
If the float switch (or water level sensor) is "OFF" with the pump running, this means the pump will stop
after 60 seconds of continuous operation, but if the float switch (or water level sensor) is switched back
to the "ON" position within 60 seconds after switching "OFF", the pump will run continuously.
•
Stopping time: if the pump stops due to low water level, it will not start within 60 seconds (even if the
float switch /or water level sensor/ is switched "ON"); the pump must be disconnected from the power
supply to restart it within 60 seconds after it has stopped
Operation recovery mode: When the pump stops due to low water level, it will restart automatically after
60 seconds if the float switch (or water level sensor) is switched "ON”.
No.
Category
Preset value
Start time
(s)
Operation
recovery time
(s)
Operation recovery mode (s)
1 Phase loss
—
2
—
Operation restored manually
(manually turn off power ---- fix
power --- turn on power, pump
starts
2
Jammed
impeller
Double rated
current
0.1
—
Operation restored manually
(manually turn off power ---- fix the
problem --- turn on power, pump
starts
3
Phase
sequence
protection
If the electrical lines
are incorrectly
connected, the
pump will not
operate
—
—
Operation restored manually
(manually turn off power ---- switch
input wire --- turn power on, pump
starts
4
Surge
protection
≥ 1.2 times rated
current
30
300
Operation restored automatically
5
Low voltage
protection
≤ 323 V
5
300
Operation restored automatically
6
Surge
protection
≥ 460 V
5
300
Operation restored automatically
7
Temperature
protection
Winding ≥ 125 ± 5
°C
0.1
—
Operation restored automatically
(winding ≤ 80 ± 10 °C)
8
Water level
control
Specified
elsewhere
—
—
—