8. Check the output voltage (the PSU voltage without load and without a battery should amount to 13,7V ÷ 13,9V, 
with a battery or during battery charging process: 11,0V÷13,8V). If the value of the voltage requires adjustment, it 
should be set by the V

ADJ

 potentiometer, monitoring the voltage at the AUX output of the PSU. 

9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -BAT black to 'minus’. The LB diode 
should be on during battery charging process. 
10. With the STOP button, activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU 
failure indication at the APS FLT output, but it does not affect the protection system against complete battery 
discharge. 
11. Check the current consumption of the receivers allowing of the battery charging current no to exceed the total 
current efficiency of the PSU. 
12. Once the tests and operation control have been completed, the enclosure can be locked. 
 
 

8. Operation and use. 

8.1. Over voltage protection OVP at the PSU output. 
In  case  of  voltage  exceeding  15.5V±0.5V  at  the  regulator’s  output,  the  system  cuts  off  the  power  at  the 

outputs to protect the battery and the receivers from damage. The outputs will be battery-powered. The protection 
system is indicated by illuminating of the OVP red LED on the pcb board, PSU FLT output status change into Hi-Z 
(high impedance), by sound and appropriate message on the PSU front panel. 

 
8.2 Overload of the PSU. 
The  PSU  has  been  equipped  with  a  LED  OVL  (overload)  indicator  light  on  the  pcb.  It  informs  about  the 

output  overload  status.  If  the  nominal  current  of  the  PSU  is  exceeded,  the  indicator  light  will  be  lit  and  the 
microprocessor  will  proceed  to  a  specially  implemented  procedure.  If  the  overload  threatens  the  PSU’s  power 
grade, the control system will decide about a disconnection of the AUX output. Restart will occur after 1 minute.  

 
8.3 Short circuit at the PSU output. 

 

In the case of a short circuit at the AUX or BAT output (load 200% ÷ 250% of the PSU power) or a reverse 

polarity  connection,  the  F

BAT

  fuse  in  the  battery  circuit  becomes  permanently  damaged  and  the  restoration  of  the 

voltage at the BAT output requires replacement of the fuse. 
 

8.4. Maintenance. 
Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU      does  not  require  performing  any  specific  maintenance  measures.  However,  in 
the  case  of  significant  dust  level,  clean  its  interior  with  compressed  air.  In  the  case  of  a  fuse replacement,  use  a 
replacement of the same parameters. 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 
 
 
 
 

Содержание PSBEN 1012B

Страница 1: ...PSBEN 1012B v 1 0 PSBEN 13 8V 1A 7Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Страница 3: ...cation of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical ou...

Страница 4: ...ime 60h if the faults of the main power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 116A 0 6A battery charge General use if the PSU is n...

Страница 5: ...om a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potenti...

Страница 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Страница 7: ...proving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presence...

Страница 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Страница 9: ...9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displayed...

Страница 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Страница 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Страница 12: ...y even after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though...

Страница 13: ...s In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without battery assistance t...

Страница 14: ...s 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequenc...

Страница 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Страница 16: ...n with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo re...

Страница 17: ...0 116A 0 6A battery charge for general use Io 1 0A 0 2A battery charge Io 0 6A 0 6A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 12...

Страница 18: ...Connectors Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 3F 2 5 30cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can be...

Страница 19: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 20: ...ers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by soun...

Страница 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Страница 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: