PSBEN1012B   

 

 

 

 
 

3.4.2 Setting the communication address. 
 

 
- press simultaneously the right and left-most buttons on the LED panel  
 
 
- the abbr ‘Adr’ will appear on the display 
 
 
 
- press the ‘>’ right arrow button  
 
 
- the abbr ‘trS’ will appear on the display  
 
 
- press ‘OK’ 
 
- now, on the display there will appear either ‘9.6’ or ‘19.2’ – values  
informing of the transmission’s speed 
 
 
- with ‘>’ or ‘<’ set the transmission’s speed to 19200,  
which is displayed as ‘19.2’  
 
 
 
 
- approve the setting with the ‘OK’ button 
 
 
 
- the abbr ‘trS’ will be displayed again 
 
 
- press the ‘>’ right arrow button  
 
 
 
 
 
- press ‘OK’ after appearing of ‘trP’ on the display 
 
 
- now, one of the following abbreviations will be displayed: ‘8n2’, ‘8E1’ or ‘8o1’ 
 
 
 
- with ‘>’ or ‘<’ set the ‘8E1’ parameter 
 
 
 
 
 
 
- approve your choice with the ‘OK’ button 
 
 
 
 
 
- finish the configuration procedure by pressing simultaneously the ’<,>’ buttons  
 
 
 

Содержание PSBEN 1012B

Страница 1: ...PSBEN 1012B v 1 0 PSBEN 13 8V 1A 7Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Страница 3: ...cation of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical ou...

Страница 4: ...ime 60h if the faults of the main power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 116A 0 6A battery charge General use if the PSU is n...

Страница 5: ...om a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potenti...

Страница 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Страница 7: ...proving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presence...

Страница 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Страница 9: ...9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displayed...

Страница 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Страница 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Страница 12: ...y even after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though...

Страница 13: ...s In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without battery assistance t...

Страница 14: ...s 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequenc...

Страница 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Страница 16: ...n with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo re...

Страница 17: ...0 116A 0 6A battery charge for general use Io 1 0A 0 2A battery charge Io 0 6A 0 6A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 12...

Страница 18: ...Connectors Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 3F 2 5 30cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can be...

Страница 19: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 20: ...ers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by soun...

Страница 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Страница 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: