3.7 Input of collective failure: EXT IN. 
The EXT IN (external input) technical input indicating a collective failure is intended for additional, external 

devices  that  generate  the  failure  signal.  If  voltage  appears  at  the  EXT  IN  input,  it  will  cause  generating  a  PSU 
failure, storing the information about the event in the internal memo and sending the signal about the failure to the 
PSU FLT output. 

The EXT IN technical input has been implemented with galvanic isolation between the PSU’s systems and the  

devices attached.  

 

Fig. 7. Electrical diagram of the EXT IN input. 

 

The electrical  diagram below shows the  way of connecting  external  devices to the EXT IN input. Outputs 

such as: OC (open collector), relay type or tamper may be used as a source of the signal. 
 

 

Fig. 8. Examples of connections. 

 

In  the  option  with  tamper  switches,  the  V

EXT

  jumper  must  be  on.  It  polarises  the  EXT  IN  input  circuit 

therefore is required in such configuration.  

The EXT IN input has been adjusted to cooperate with fuse modules that generate a failure signal in case 

of a fuse fault in any of output sections (e.g. AWZ535, AWZ536). To guarantee a correct cooperation between the 
module and the EXT IN input, the V

EXT

 jumper must be on and the connections are to be made accordingly to the 

diagram below. 

 

Fig. 9. Example of a connection with the fuse module: AWZ535 or AWZ536. 

 

4. Battery-assisted operation. 

4.1. Running the PSU from the battery. 

 

The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the 

PSU during battery-assisted operation. 

 

Running the PSU from the battery: press the START button on the main board and hold for 1s. 

 

Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s. 

 
 

 

Содержание PSBEN 1012B

Страница 1: ...PSBEN 1012B v 1 0 PSBEN 13 8V 1A 7Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Страница 3: ...cation of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical ou...

Страница 4: ...ime 60h if the faults of the main power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 116A 0 6A battery charge General use if the PSU is n...

Страница 5: ...om a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potenti...

Страница 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Страница 7: ...proving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presence...

Страница 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Страница 9: ...9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displayed...

Страница 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Страница 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Страница 12: ...y even after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though...

Страница 13: ...s In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without battery assistance t...

Страница 14: ...s 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequenc...

Страница 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Страница 16: ...n with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo re...

Страница 17: ...0 116A 0 6A battery charge for general use Io 1 0A 0 2A battery charge Io 0 6A 0 6A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 12...

Страница 18: ...Connectors Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 3F 2 5 30cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can be...

Страница 19: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Страница 20: ...ers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by soun...

Страница 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Страница 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Отзывы: