Page14
Parameter Defaults
Factory Defaults
Factory Defaults
When first installing the
IMP Lite
, or subsequently moving or using the unit
on a new application, before proceeding to program the unit for its intended
application it is recommended that you ensure that all parameters are at their
default values by completing a
Factory Defaults P930,
as described in
Chapter 5
Parameter Guide
.
When you first switch the
IMP Lite
on, it will be reading the
distance
from the
face of the transducer to the material surface. It will be indicating in
P104
Measurement Units
, as shown on the display.
TIP
In some applications, it is simplest to empty
the vessel, take a reading from the Imp for
distance and then setup the empty level to
this figure.
Once you are satisfied with the installation, and the
IMP Lite
is reading what
you would expect in terms of distance from the face of the transducer to the
material level, then you can proceed with programming, for the intended
application. It is sensible to program all of the required parameters at the same
time. The system will be then set-up.
Note The span is automatically calculated from the empty level, so the empty
level should be entered first.