P213 (Relay 1), P223 (Relay 2) - Relay “ON” Setpoint
This parameter determines the “
ON
” point for the alarm and should be set as
follows, in
Measurement Units P104
High Alarm
Low Alarm
P213/P223
“
ON
” Setpoint
P213/P223
“
ON
” Setpoint
Higher than Lower than
P214/P224
“OFF” Setpoint P214/P224
“OFF” Setpoint
P214 (Relay 1), P224 (Relay 2) - Relay “OFF” Setpoint
This parameter determines the “
OFF
” point for the alarm and should be set as
follows, in
Measurement Units P104
High Alarm
Low Alarm
P214/ P224
“
OFF
” Setpoint
P214/ P224
“
OFF
” Setpoint
Lower than Higher than
P213/P223
“ON” Setpoint P213/P223
“ON” Setpoint
LOE (Loss Of Echo))
No setpoints are required when relays are used as LOE (Loss Of Echo)
Control
P210 (Relay 1), P220 (Relay 2) =2 (Control)
P211 (Relay 1), P221 (Relay 2) - Relay Function
,
This parameter defines whether the
general
control
relay function is
currently “ON” or “OFF”.
General Control
Description
0= Off (Default)
Relay is always de-energised.
1= On
Control is based on the level in the vessel. All
general controls are used to assist each other (run at
the same time) and each general control has its own
“ON” and “OFF” setpoints.