Page 26
P106 Span
This parameter should be set to the maximum distance from the
Empty
Level
(
P105
) to the maximum material level. It is automatically set to be
equal to the
Empty
Level
(
P105
) less the
Near
Blanking
distance (
P107
),
when you set the empty level.
Default IMP 3 = 2.80m (9.19 feet), IMP 6 =
5.70m (18.70 feet)
and
IMP 10 = 9.70m (31.82 feet).
P107 Near Blanking Distance
This parameter is the distance from the face of the transducer that is not
measurable, and is pre-set to the minimum value dependant on the version
of
IMP+
IMP+
IMP+
IMP+
being used. It should not be set to less than this figure, but can be
increased.
IMP+
IMP+
IMP+
IMP+
Version
Near Blanking Distance
IMP 3 metre
Default Blanking Distance = 0.2m (0.66 feet)
IMP 6 metre
Default Blanking Distance = 0.3m (0.98 feet)
IMP 10 metre
Default Blanking Distance = 0.3m (0.98 feet)
P108 Far Blanking Distance
This is the distance (as a
percentage
of empty level) beyond the empty
point that the unit will be able to measure, and the
default
is pre-set to
10%
of the empty level.
If the surface being monitored can extend beyond the
Empty
Level
(
P105
)
then the far blanking distance can be increased to a maximum of 100% of
empty level.
This parameter is always entered as a % of empty level.