There are three
types
that each relay, individually, can be set to, for
example, consider
Relay 1
, you can select parameter
P210
from the
following options:
0 = Not in Use
r
elay will remain in the de-energised condition.
1=Alarm
:
relay will de-energise to set the alarm “ON”.
2=Control
relay will energise to set the control “ON”.
Alarm Relay Set-up
The alarm relays are de-energised to turn the alarms “ON”, and energised to
turn the alarms “OFF”. In this way, loss of power will ensure that the alarm
is activated.
To set an
alarm
relay, set the
first parameter
for the relay to equal
1
E.g.
Setting
Relay 1
for alarm purposes
P210 = 1
Setting
Relay 2
for alarm purposes
P220 = 1
The
second parameter
for each relay determines the
function
of the alarm
relay, using the example of
Relay 1
, the
alarm function
can be selected
from the options available in parameter
P211
.
For full details of all available alarm options please refer to
P211, 221 Relay
Function…
If P210, 220 = 1(Alarm)
tables in Chapter 5.
The
third parameter
, and the
fourth parameter
for each relay set the
Alarm
“
ON
” and “
OFF
” points. For a
high alarm
then set “
ON
”
higher
than
“
OFF
”. For
low alarm
then set “
ON
”
lower than
“
OFF
”. Using the
example of
Relay 1
P213
and
P214
set the
“ON”
and
“OFF”
points.
For example using
Relay 1
High Alarm
Low Alarm
P213
“ON” Setpoint
P213
“ON” Setpoint
Higher than Lower than
P214
“OFF” Setpoint
P214
“OFF” Setpoint