Chapter 5
Parameter Guide
Parameter Listing
This chapter describes all of the parameters contained within the
IMP+
IMP+
IMP+
IMP+
.
Application (APP) Menu
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be set
to one of the following:
Option
Description
1=
Distance (Default)
Display shows the distance from the
transducer face to the surface.
2= Level
Display shows how full the vessel is.
3= Space
Display shows how empty a vessel is.
4= Volume
Display shows volume of material in the
vessel
P104 Measurement Units
This parameter sets the units you want to use for programming and display
Option
Description
1 = metres
All units of measure are
METRES
2 = cm
All units of measure are
CENTIMETRES
3 = mm
All units of measure are
MILLIMETRES
4 = feet
All units of measure are
FEET
5 = inches
All units of measure are
INCHES
P105 Empty Level
This parameter is to be set to the maximum distance from the face of the
transducer to the empty point, in
P104
Measurement
Units
. Note this value
affects span as well, so should be set before span.
Default: IMP 3 = 3.00m
(9.84 feet), IMP 6 = 6.00m (19.69 feet)
and
IMP 10 = 10.00m (32.81 feet)
.