3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 

connected  to  ground  (L  level 

–  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 

impedance state hi-Z. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay 

contacts. 
 

 

CAUTION!

 In Fig.5. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-  OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected 

to ground  (L  level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is 

switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.5.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

LoB 

– technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 11,5V) the output is connected to ground (L level 

– 0V). In case 

of decrease of battery voltage (U

BAT

 < 11,5V) the output is switched into high impedance state 

– hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 11,5V, the contacts of the relay change over. 

 
 

CAUTION! 

In the Fig.5. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5V). 

 

 
 

 

 

Fig. 4. Electrical diagram of OC outputs. 

Fig. 5. Electrical diagram of relay outputs. 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание GREEN POWER plus HPSBOC 20A12E

Страница 1: ...HPSBOC 20A12E v 1 0 HPSBOC 13 8V 20A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 1 from 04 03 2015 Supercedes edition GREEN POWER plus...

Страница 2: ...tallation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnect...

Страница 3: ...tput indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC typ...

Страница 4: ...2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Fig 3 The view of the PSU 1 4 Specifications electrical parameter...

Страница 5: ...indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status DC diode indicating DC power status at...

Страница 6: ...llation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and n...

Страница 7: ...and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the po...

Страница 8: ...ut is connected to ground L level 0V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contac...

Страница 9: ...ipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5 V at the battery terminals will cause battery disconnection 4 3 Maintenance Any...

Страница 10: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...

Отзывы: