Pulsar GREEN POWER plus HPSBOC 20A12E Скачать руководство пользователя страница 2

www.pulsar.pl                                                      HPSBOC20A12E                                                           

GREEN POWER plus

  

 

 

2

 

Features: 

 

 

DC 13,8V/20A uninterruptible power supply

*

  

 

fitting battery: 65Ah/12V  

 

wide range 

of mains supply: 176÷264V  

 

built-in power factor correction system (PFC) 

 

high efficiency 85% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

jumper selectable battery charge current 
2A/4A/8A 

 

battery output full protection against short-circuit 
and reverse polarity connection  

 

LED indication  

 

 

EPS technical output indicating AC power loss  

     

– OC and relay type 

 

PSU technical output indicating PSU failure       

      

– OC and relay type 

 

LoB technical output indicating battery low voltage   
– OC and relay type 

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage 

protection (AC input) 

 

against sabotage 

 

overload protection OLP 

 

overheat protection OHP 

   forced cooling - built-in fan 

 

warranty 

– 2 year from the production date 

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 

Disconnection of discharged battery 

4.3 Maintenance 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 

12V DC 

 (+/-15%).

 The PSU provides voltage of 

U=13,8V DC.

 Current efficiency: 

 

1.  Output current 18A + 2A battery charge

*

 

2.  Output current 16A + 4A battery charge

*

  

3.  Output current 12A + 8A battery charge

*

  

                                        Total device c battery: 20A max

*

 

In case of power decay 230V, a battery back-up is activated immediately. The PSU is constructed based 

on the switch mode PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) 
which can accommodate a 65Ah/12V battery.  

The power supply is equipped with relay and the OC type technical outputs indicating power failure, the 

failure of the power supply and low battery voltage.  

A micro switch indicates door opening (front cover). 

 

The power supply housing has space for additional modules (fuse blocks, voltage regulators and DC-DC 
converters). Optional power supply configurations are available at the website

www.pulsar.pl

 

 
 
 

 

                                                 

*

 

See chart 1

 

Содержание GREEN POWER plus HPSBOC 20A12E

Страница 1: ...HPSBOC 20A12E v 1 0 HPSBOC 13 8V 20A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 1 from 04 03 2015 Supercedes edition GREEN POWER plus...

Страница 2: ...tallation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnect...

Страница 3: ...tput indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC typ...

Страница 4: ...2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Fig 3 The view of the PSU 1 4 Specifications electrical parameter...

Страница 5: ...indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status DC diode indicating DC power status at...

Страница 6: ...llation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and n...

Страница 7: ...and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the po...

Страница 8: ...ut is connected to ground L level 0V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contac...

Страница 9: ...ipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5 V at the battery terminals will cause battery disconnection 4 3 Maintenance Any...

Страница 10: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...

Отзывы: