Pulsar GREEN POWER plus HPSBOC 20A12E Скачать руководство пользователя страница 3

www.pulsar.pl                                                      HPSBOC20A12E                                                           

GREEN POWER plus

  

 

 

3

 

 
 
1.2 Block diagram (fig.1). 

 

 

 

                                                       Fig.1. The block diagram of the PSU. 

1.3 Description of 

the module’s components and connectors (tab.1, fig.2). 

Table 1.  Elements of the 

module’s (see fig. 2). 

Element no. 

Description 

[1] 

LED indicating presence of AC power

  

[2] 

LED indicating presence of DC power 

[3] 

LED indicating correct battery voltage 

[4] 

EPS -

 AC absence technical output 

– relay type 

[5] 

PSU -

 output indicating DC absence/PSU failure 

– relay type

 

[6] 

LoB- 

output indicating battery low voltage 

– relay type 

[7] 

EPS -

 AC absence technical output 

– OC  type 

[8] 

PSU -

 output indicating DC absence/PSU failure - OC  type

 

[9] 

LoB - 

output indicating battery low voltage - OC  type 

[10] 

Connectors PSU: 
V+, V-

 DC power output 

B+, B- 

terminals for battery connection 

L-N  

power supply connector 230V AC,  

 Protection connector PE

 

[11] 

V

ADJ

 - potentiometer,

 

DC voltage adjustment

 

[12] 

Selection jumper for charging current: 

 
 

       Ibat =2 A,                 Ibat=4A              Ibat=8A   

 

Description

 

jumper installed, 

  

jumper removed 

[13] 

Battery connectors: red: +,  black: - 

[14] 

LED indication

 on the front panel

 

 

Содержание GREEN POWER plus HPSBOC 20A12E

Страница 1: ...HPSBOC 20A12E v 1 0 HPSBOC 13 8V 20A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 1 from 04 03 2015 Supercedes edition GREEN POWER plus...

Страница 2: ...tallation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnect...

Страница 3: ...tput indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC typ...

Страница 4: ...2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Fig 3 The view of the PSU 1 4 Specifications electrical parameter...

Страница 5: ...indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status DC diode indicating DC power status at...

Страница 6: ...llation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and n...

Страница 7: ...and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the po...

Страница 8: ...ut is connected to ground L level 0V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contac...

Страница 9: ...ipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5 V at the battery terminals will cause battery disconnection 4 3 Maintenance Any...

Страница 10: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...