Pulsar GREEN POWER plus HPSBOC 20A12E Скачать руководство пользователя страница 5

www.pulsar.pl                                                      HPSBOC20A12E                                                           

GREEN POWER plus

  

 

 

5

 

W

H

D

  Table 3. Electrical parameters  

PSU type 

A (EPS - External Power Source) 

Mains supply 

176÷264V AC   50Hz 

Current up to 

1,5A@230VAC  max.  

Supply power 

300W max.  

Efficiency 

85% 

Power factor PF 

>0,95 @230V AC 

Output voltage 

11V÷ 13,8V DC – buffer operation 
9,5V÷13,8V DC – battery-assisted operation 

Output current t

AMB

<30°C 

18A + 2A battery charge - see chart 1 
16A + 4A battery charge - see chart 1 
12A + 8A battery charge - see chart 1 

Output current t

AMB

=40°C 

12A + 2A battery charge - see chart 1 
10A + 4A battery charge - see chart 1 
 6A + 8A battery charge - see chart 1 

Voltage adjustment range 

12

÷14VDC 

Ripple 

120mV p-p max. 

Current consumption by PSU systems  

230 mA 

Battery charge current 

2A, 4A or 8A 

– jumper selectable 

Short-circuit protection SCP 

electronic, automatic recovery 

Overload protection OLP 

105-150% of power supply, automatic recovery 

Battery circuit protection SCP and reverse 
polarity connection 

melting fuse 30A 

Surge protection 

varistors 

Overvoltage protection OVP 

>16V (activation requires disconnecting the load or supply 
for about 20 s.) 

Excessive discharge protection UVP 

U<9,5 V (

± 5%) – disconnect of connection battery 

Tampering protection system: 
- TAMPER 

– indicating unwanted opening of the 

PSU’s enclosure 

- a microswitch, NC contacts (enclosure closed) 0,5A@50V 
DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- DC diode indicating DC power status at 
the PSU output 
- BAT diode indicating battery voltage level 

- red, normal status 

– on, failure: off 

- green, normal status 

– on, failure: off 

 
- green, normal status 

– on, failure: off 

Technical outputs: 
- EPS; output indicating AC power failure 
 
 
 
 
- PSU; output indicating DC absence/PSU failure 
 
 
 
- LoB output indicating battery low voltage 
 
 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
- OC type, 50mA max., normal status: L (0V) level, failure: 
hi-Z level, 
 
 
- relay type: 1A@ 30VDC/50VAC 
- OC type, 50mA max., normal status: L (0V) level, failure: 
hi-Z level  
 
- relay type: 1A@ 30VDC/50VAC 
- OC type, 50mA max., normal status: (U

BAT

 >11,5V): L (0V) 

level, 
 failure: (U

BAT

 <11,5V): hi-Z level 

 

  Table 4. Mechanical parameters  

Enclosure dimensions 

400 x 350 x 170+8 (WxHxD) [mm] 

Fixation 

See figure 3 

Fitting battery 

65Ah/12V (SLA) max. 
360x175x165mm (WxHxD) max  

Net/gross weight 

6,8kg / 7,2kg 

Enclosure  

Steel plate, DC01 1,0mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10),  
Technical output

: Φ0,41-1,63 (AWG 26-14) 

Battery output BAT: 

Ф6/2,5mm

2

 

TAMPER output: wires 

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 
Forced cooling - built-in fan. 

Содержание GREEN POWER plus HPSBOC 20A12E

Страница 1: ...HPSBOC 20A12E v 1 0 HPSBOC 13 8V 20A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 1 from 04 03 2015 Supercedes edition GREEN POWER plus...

Страница 2: ...tallation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnect...

Страница 3: ...tput indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC typ...

Страница 4: ...2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Fig 3 The view of the PSU 1 4 Specifications electrical parameter...

Страница 5: ...indicating unwanted opening of the PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status DC diode indicating DC power status at...

Страница 6: ...llation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and n...

Страница 7: ...and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the po...

Страница 8: ...ut is connected to ground L level 0V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contac...

Страница 9: ...ipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5 V at the battery terminals will cause battery disconnection 4 3 Maintenance Any...

Страница 10: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...

Отзывы: