3.1   Optical  indication: 
 

 
 
 
 
 
 

 

 
 

 
 

Number 

of blinks 

Type of failure 

Causes 

Remarks 

1 Battery 

damaged 

Discharged battery, battery 

not connected, battery fuse 

blown 

Check the connection and 

the fuse of battery 

2 Batter 

discharged 

Indicates the drop of the 

battery voltage to  

below 10 V 

During operation from 

battery 

Output voltage too low < 

10V 

Output overloaded 

Remove the condition of 

the overload and connect 

after 30 s 

Output voltage to high   > 

14.5V 

The voltage stabilizer 

damaged, incorrect setting 

of trimming potentiometer 

 

Overheating of the power 

supply unit board 

Temperature of board > 

120°C 

 

Tab.1. 

 

3.2 Acoustic indication: 

The buzzer acoustically indicates the failure conditions.The frequency and number of signals depend 
on the type of failure (Tab.2). The acoustic indication can be disabled by the jumper 

ZB

 

No. 

Description 

Event 

1 signal every 8 s 

Operation from battery, power supply 230 VAC shortage 

2 signals every 16 s 

Discharged battery, no battery during operation from the 

mains, battery fuse blown 

Fast signals during 3s 

Restart of the power supply unit 

12 signals 

Battery test disabled 

3 signals 

Battery test enabled 

6 Continuous 

signal  Failure, the type of failure indicated by: RED LED 

Tab.2. 

 

3.3 Indication outputs. 

The power supply unit is equipped with indication outputs informing about the power supply shortage 
and failures. 

 

AW – failure output:

 output (OC type) informing about the failures of the power supply unit  

In the normal state, when there is no failures, the output is closed and it opens if a failure occurs.  

 

BS- Power supply 230 VAC shortage output 

:  output (OC type) informing about the 

shortageof power supply 230 VAC in the normal mode, during the operation from 230 VAC the output 

RED LED 

 

blinking- indication of failure conditions ( Tab.1) 

 

GREEN LED 

 

lit- power supply unit operated from 230 V/AC, normal 
operation  

 

blinking- shortage of power supply 230 V/AC, operation 
from battery

 

Содержание AWZ 230

Страница 1: ...ZBPK 13 8V 2A 7Ah AWZ 230 Zasilacz buforowy Buffer power supply unit Z lo n zdroj Alimentation tampon ver PL EN CZ FR 20060725...

Страница 2: ...pi cie w obwodzie zasilaj cym 230V jest od czone 2 Zamontowa zasilacz w wybranym miejscu i doprowadzi przewody po czeniowe 3 Wyj bezpiecznik sieciowy zabezpieczaj cy obw d pierwotny transformatora 15...

Страница 3: ...aniu testu akumulatora 10 min 13 Przy pomocy przycisku STOP 3 w czy lub wy czy dynamiczny test akumulatora Wy czenie testu wy cza r wnie sygnalizacj awarii akumulatora na wyj ciu 14 Na ko kach ZB 2 ok...

Страница 4: ...j cie brak zasilania 230V AC wyj cie typu OC sygnalizuje utrat zasilania 230V AC w stanie normalnym przy zasilaniu 230V wyj cie jest rozwarte w przypadku utraty zasilania zasilacz za czy wyj cie po up...

Страница 5: ...ly unit provides voltage with less noise and shorter time of fault response when compared to a pulse stabilizer The supply unit provides the voltage VDC 12V 13 8V DC and the output current of IMAX 2A...

Страница 6: ...he output becomes disconnected from the mass 7 With the switching pieces Z3 Z4 5 determine the time of disconnecting the battery in the case of battery assisted operation when the voltage on the termi...

Страница 7: ...peration from battery power supply 230 VAC shortage 2 2 signals every 16 s Discharged battery no battery during operation from the mains battery fuse blown 3 Fast signals during 3s Restart of the powe...

Страница 8: ...battery The battery disconnection time is set by jumpers Z3 Z4 Tab 4 Tab 4 4 3 Dynamic test of battery charge Every 10 minutes the unit executes the battery test by lowering the input voltage and mea...

Страница 9: ...pojte ke svorce ozna en symbolem uzemn n Spojen se prov d troj ilov m kabelem se lutozelen m uzem ovac m vodi em PE Nap jec vodi e p ive te izola n pr chodkou k p slu n m svork m transform toru 14 16...

Страница 10: ...ch stav 3 1 Optickou signalizac Po et problikn ut Typ poruchy P ina Pozn mky 1 chyba akumul toru Akumul tor nen nabit akumul tor nen p ipojen pojistka akumul toru je sp len Zkontrolovat spoje a pojis...

Страница 11: ...Tab 3 4 Pr ce z akumul toru 4 1 Start pr ce zdroje z akumul toru Doba provozu p i nap jen z akumul toru z vis na jeho kapacit rovni nabit a zat ovac m proudu Nap klad u typick ho pln nabit ho akumul t...

Страница 12: ...basse tension Avant de commencer l installation il faut faire le bilan de charge pr vue pour l alimentation Pendant une utilisation normale la somme des courants consomm s par les appareils r cepteurs...

Страница 13: ...r le test dynamique de la batterie Tab 2 Le fait de d brancher le test d branche galement la signalisation des avaries de la batterie sur la sortie AW mais ne d branche pas le syst me de protection de...

Страница 14: ...signal toutes les 8s Fonctionnement sur la batterie absence d alimentation 230V AC 2 2 signaux toutes les 16s Batterie insuffisamment charg e absence de batterie pendant le fonctionnement sur secteur...

Страница 15: ...e La dur e de temporisation jusqu au d branchement de la batterie est r gl e l aide des cavaliers Z3 Z4 Tab 4 Tab 4 4 3 Test dynamique de charge de la batterie Toutes les 10 min l appareil proc de un...

Страница 16: ...fig 1...

Страница 17: ...bezpiecznik w obwodzie akumulatora F1 fuse in the battery circuit F1 pojistka v obvodu akumul toru F1 fusible dans le circuit de la batterie 14 230V 0V z cze zasil 230V AC 230V 0V terminals 230V AC 2...

Страница 18: ...ary windings of the transformer max Proud v prvotn m obvodu transform toru max Courant du circuit primaire du transformateur max 320 mA Zabezpieczenie termiczne transformatora Thermal protection of th...

Страница 19: ...t rej dotyczy reklamacja GUARANTEE 24 months from the date of sale 36 months from the date of production THE GUARANTEE IS VALID only upon presenting the sale invoice for the unit for which the claim i...

Отзывы: