Fig. 20. Example of a connection with the fuse module EN54-LB8.
6.7. Indication of the enclosure opening - TAMPER.
The PSU is fitted with the microswitch tamper indicating enclosure opening.
The tamper cable is not connected to the terminal in the factory settings. In order to activate tamper,
remove the jumper from tamper terminal (Fig. 2 [12]) and plug in the tamper cable.
Each opening the enclosure will generate a failure signal at the PSU FLT and ALARM technical outputs
and will save the event in the internal memory of the PSU.
6.8. Increasing the number of outputs with optional EN54-LB4 or EN54-LB8 fuse
modules.
The PSU has two independently protected outputs for connecting the AUX1 and AUX2 receivers.
If the power supply unit is connected with more receivers, then it is recommended to secure each of them with
independent fuse. This solution will protect the power supply system, while the damage to only one receiver (short-
circuit on the line) could cause damage to other receivers connected to the same output.
The solution is provided by the optional fuse module EN54-LB4, 4-channel or EN54-LB8, 8-channel, while
its mounting location is provided within the housing (see Fig. 4). The figure below shows the connection between
the power supply, fuse module and receivers.
Fig.21. The connection of fuse module.