6.4.6. List of failure codes and information messages.
The PSU indicates the operation status with the appropriate code. The codes are divided into two
groups,
marked with the initial letters "F" or "
I”.
The codes beginning with the letter "F" indicate a failure. The codes that begin with the letter "I" indicate the
correct operation of the PSU or repaired fault, involving, for example, fuse replacement: "I03 - BAT fuse
replaced”.
Table 9. List of PSU failure codes.
Failure
code
Information
Technical output
activation
Causes
Additional
information
F01
AC power fail!
EPS FLT,
ALARM
- No AC mains supply
- Blown F
MAIN
fuse
F02
AUX1 fuse fail!
PSU FLT,
ALARM
- Blown F
AUX1
fuse
AUX2 fuse fail!
- Blown F
AUX2
fuse
F03
BAT fuse fail!
APS FLT, ALARM
- Blown F
BAT
fuse
- Short circuit in the battery circuit
- Short circuit in the AUX output circuit
F04
Output overload!
PSU FLT,
ALARM
- PSU overload
See section 6.10
F05
Battery
undercharged!
APS FLT,
ALARM
- Spent batteries
- Undercharged batteries
See section 8
F06
High AUX1
voltage!
PSU FLT,
ALARM
- Output voltage over 29.2V
High AUX2
voltage!
F08
Charge circuit fail!
PSU FLT,
ALARM
- The output voltage of the PSU set too low ,
below 26V
- Battery charging circuit failure
F09
Low AUX1
voltage!
PSU FLT,
ALARM
- Output voltage below 26V
Low AUX2
voltage!
F10
Low battery
voltage!
APS FLT,
ALARM
- The battery voltage has dropped below
23V (during battery-assisted operation
F11
Low battery volt.
–
off!
APS FLT,
ALARM
- the battery voltage has dropped below 20V
(during battery-assisted operation)
See section 8.4
F12
External input
EXTi!
ALARM
- Activation of the input of collective failure:
EXTi
See section 6.6
F14
Temp. sensor
fault!
PSU FLT,
ALARM
- Faulty temperature sensor
- Temperature sensor disconnected
See section 8.7
F15
High battery
temp.!
PSU FLT,
ALARM
- Too high ambient temperature of the PSU.
- Overloaded batteries.
- Faulty batteries.
See section 8.7
F16
No battery!
APS FLT,
ALARM
- Disconnected batteries
See section 8.1
F17
Battery fail!
APS FLT,
ALARM
- Deeply discharged batteries, voltage below
20V
See section 8
F18
High batt. circuit
resist.!
APS FLT,
ALARM
- Spent batteries
- Loose cables connecting the batteries
See section 8.6
F19
High AC voltage!
PSU FLT,
ALARM
- Mains supply over 254V AC
F20
Low AC voltage!
PSU FLT,
ALARM
- Mains supply below 195V AC
F21
PSU cover
opened!
PSU FLT,
ALARM
See section 6.7
F50-F54
Internal supply fail!
PSU FLT,
ALARM
- service codes
F60
No communication
PSU FLT,
ALARM
- no communication with LCD panel
F61-F64
Control panel fail
PSU FLT,
ALARM
- service codes
F65
Access unlocked
- passwords unlocked