![Pulsar Measurement Ultra 3 Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/pulsar-measurement/ultra-3/ultra-3_instruction-manual_1625418067.webp)
PULSAR MEASUREMENT
67
To program the Ultra 3 for
Example 2 Sump control (pump down) b
y
using the
Quick Setup
menu proceed as follows. If required to access
Program Mode,
key in the
passcode
1997
and press
ENTER
At the
Quick Setup
menu press
ENTER
and as prompted, by the questions,
select the relevant option and
ENTER
.
QUESTION
OPTION
Level/Pump/Custom
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
Type Alarm 1
1 = High Alarm
Alarm No. 1
5 = Set to relay 5
Xducer (P101)
2 = dB6
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
, and the Ultra 3 will return to the
Run Mode
.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can
be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is
displayed, and entering new values to relay setpoints as required. Alternatively,
the relevant relay setpoint can be accessed either by the main menu system or
directly via parameter number and changed as necessary.
Содержание Ultra 3
Страница 1: ...Ultra 3 Instruction Manual...
Страница 14: ...ULTRA 3 INSTRUCTION MANUAL 14 EU Certificate of Conformity...
Страница 18: ...ULTRA 3 INSTRUCTION MANUAL 18 The full dimensions of the enclosure are as shown below...
Страница 22: ...ULTRA 3 INSTRUCTION MANUAL 22 Dimensions of the panel enclosure are as shown below...
Страница 178: ...ULTRA 3 INSTRUCTION MANUAL 178 NOTES...