ULTRA 3
INSTRUCTION MANUAL
154
mA Failsafe
P840 mA Failsafe Mode
This parameter determines what happens to the mA output in the event of
the unit going into fail-safe mode. The
default
is to do the same as the
system fail-safe
(
P808
), but this can be overridden to force the mA output
to an independent fail-safe mode as follows:
OPTION
DESCRIPTION
0 = Default
mA output will fail as per
P808
1 = Hold
mA output will retain its last known value.
2 = Low
mA output will fail to its
low
condition.
3 = High
mA output will fail to its
high
condition.
P841 mA Allocation
By default, the mA output will be representative of the reading obtained, as
determined by the
Mode P100
. When
P100
=
5
(Volume)
the output can
be assigned to be representative of the
level
. This parameter is
automatically set to the correct default option when selecting the
Mode
P100
and
under normal circumstances will not require changing.
The options, dependant on the
value
entered for
Mode P100
, are as
follows:
OPTION
DESCRIPTION
2 = Xducer 1 (Default)
mA output relates to Xducer 1 levels
When Ultra Wizard = 1 Level/Volume
5 = Volume
mA output relates to the
Volume
Содержание Ultra 3
Страница 1: ...Ultra 3 Instruction Manual...
Страница 14: ...ULTRA 3 INSTRUCTION MANUAL 14 EU Certificate of Conformity...
Страница 18: ...ULTRA 3 INSTRUCTION MANUAL 18 The full dimensions of the enclosure are as shown below...
Страница 22: ...ULTRA 3 INSTRUCTION MANUAL 22 Dimensions of the panel enclosure are as shown below...
Страница 178: ...ULTRA 3 INSTRUCTION MANUAL 178 NOTES...