General Control
When Ultra Wizard = 1 Level/Volume
P210, 220, 230 = 2 (General Control)
When a relay is being set up as a
control
relay, the
second parameter
that
will be displayed in the menu determines its
function.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = On
Control is based on the level in the vessel. All general
controls are used to assist each other (run at the same time)
and each general control has its own “ON” and “OFF”
setpoints.
The
third parameter
has
no function
when
general control
is chosen and
will not be displayed.
The
fourth parameter
and
fifth parameter
are set to determine the switch
points for the
general control
relay.
See the
general control
function, table
(
P211, 221, 231
) for further information.
P213, P223, P233 - Relay Setpoint 1
This parameter determines the “
ON
” point for the general control relay, relay
Setpoints are entered in values of Measurement Units (
P104
)
P214, P224, P234 - Relay Setpoint 2
This parameter determines the “
OFF
” point
for the general control relay,
relay Setpoints are entered in values of Measurement Units (
P104
)
Important Notice
The General control relays are started and stopped at the “
ON
” and “
OFF
”
setpoints. To
control down
(reduce level) then set “
ON
”
higher than
“OFF”. To
control up
(increase level) then set “
ON
”
lower than
“
OFF
”.
Содержание Ultra 3
Страница 1: ...Ultra 3 Instruction Manual...
Страница 14: ...ULTRA 3 INSTRUCTION MANUAL 14 EU Certificate of Conformity...
Страница 18: ...ULTRA 3 INSTRUCTION MANUAL 18 The full dimensions of the enclosure are as shown below...
Страница 22: ...ULTRA 3 INSTRUCTION MANUAL 22 Dimensions of the panel enclosure are as shown below...
Страница 178: ...ULTRA 3 INSTRUCTION MANUAL 178 NOTES...