![Pulsar Measurement Ultra 3 Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/pulsar-measurement/ultra-3/ultra-3_instruction-manual_1625418109.webp)
PULSAR MEASUREMENT
109
When Ultra Wizard = 3 Flow
1 = dB Mach3
(Default
Transducer is a dB Mach3. Range = 0 to 2.425 metres
2 = dB6
Transducer is a dB6. Range = 0.3 to 6 metres
3 = dB10
Transducer is a dB10. Range = 0.3 to 10 metres
4 = dB15
Transducer is a dB15. Range = 0.5 to 15 metres
7 = dBS6
Transducer is a dBS6. Range = 0.2 to 6 metres
Available for all Ultra Wizard options
*11 = dBR16
Transducer is a mmWave radar. Range 0.077 to 16 metres
*12 = dBR8
Transducer is a mmWave radar. Range 0.077 to 8 metres
P102 Material
This parameter should be set to the type of material being monitored.
OPTION
DESCRIPTION
1 = Liquid (Default)
Used for liquids and flat solid materials.
2 = Solid
Used for sold material that is heaped or at an angle.
3 = Closed Tank
Use for applications within a closed tank or where a
secondary echo response may become focused to
create a larger echo than the first.
Dimensions
P104 Measurement Units
This parameter sets the units you want to use for programming and display.
OPTION
DESCRIPTION
1 = metres (Default)
All units of measurement are
Metres
2 = cm
All units of measurement are
Centimetres
3 = mm
All units of measurement are
Millimetres
4 = feet
All units of measurement are
Feet
5 = inches
All units of measurement are
Inches
Important Notice
*Please consult your local Pulsar distributor for the versions of firmware that the
mmWAVE radars are available in.
Содержание Ultra 3
Страница 1: ...Ultra 3 Instruction Manual...
Страница 14: ...ULTRA 3 INSTRUCTION MANUAL 14 EU Certificate of Conformity...
Страница 18: ...ULTRA 3 INSTRUCTION MANUAL 18 The full dimensions of the enclosure are as shown below...
Страница 22: ...ULTRA 3 INSTRUCTION MANUAL 22 Dimensions of the panel enclosure are as shown below...
Страница 178: ...ULTRA 3 INSTRUCTION MANUAL 178 NOTES...