MLY02.100

 

MiniLine

 

MLY-Series 

DC12-48V

 

(120V),

 

10A,

 

D

UAL 

R

EDUNDANCY 

M

ODULE

 

 

 

3.

 

I

NPUT AND 

O

UTPUT 

C

HARACTERISTICS

 

 

Number of inputs 

 

Number of outputs 

 

Input voltage 

nom. 

DC 12-48V 

±25%

 

The input circuitry must meet the SELV requirements 
stipulated by IEC/EN/UL 60950-1. 

Input voltage range 

9–60Vdc 

 

Input voltage with restrictions 

nom. 

DC 12-120V 

±25%

 

See note 3 on bottom of the table 

Input voltage range  
with restrictions 

9-150Vdc 

Restrictions apply, see note 3 on bottom of the table. 

at 2x2.5A, see Fig. 3-2

Voltage drop, input to output 

typ. 

0.8V 

 

 

typ. 

0.9V 

at 1x5A, see Fig. 3-3

 

 

 

typ. 

0.9V 

at 2x5A, see Fig. 3-2

Input current 

nom. 

2x 0-5A 

continuous 

 

nom. 

1x 0-10A 

continuous, see note 1 

 

nom. 

2x 5-8A 

for 5 seconds 

Peak input current 

max. 

125A 

for maximal 10ms per input 

Output current 

nom. 10A 

continuous 

 

nom. 

10-16A 

for 5 seconds 

 max. 

16A at 

continuous 

overload 

or short circuit, see note 2 

Reverse current 

max. 

0.6mA 

per input, -40°C to +60°C 

Reverse voltage 

max. 

200Vdc 

voltage applied to the output, continuously allowed 

Note 1: 

Each input can be loaded up to 10A. At currents above 10A, the other input should not be loaded. It is preferable to parallel the two 
inputs in order to minimize the power loss in such cases. 

Note 2: 

Ensure that the continuous output current does not exceed 16A. Check the short-circuit current of the power sources and if the 
power source can deliver more than 16A together, use an appropriate fuse on the output. 

Note 3: 

The redundancy module can be used with input voltages up to 150Vdc with the constraint, that it can be used only as a single input 
module at voltages above 60Vdc. Both inputs need to be connected together as shown in Fig. 3-1. Ensure proper means to protect 
against touching this voltage. 

 

 

Fig. 3-1

   Restrictions for utilizing voltages between 60 and 150Vdc (See also Note 3) 

 

AC

DC 

(>60V)

+

-

Load

>60V

+

-

Power Supply

Power Supply

Diode Module

+

-

+

+

-

-

AC

DC 

(>60V)

+

-

 

AC

DC 

(>60V)

+

-

Load

>60V

+

-

Power Supply

Diode Module

+

-

+

+

-

-

Diode Module

+

-

+

+

-

-

AC

DC 

(>60V)

+

-

Power Supply

 

 

Apr. 2014 / Rev. 1.3 DS-MLY02.100-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 

  

   

4/16

Содержание MiniLine MLY-Series

Страница 1: ...low a safe and fast installation and a large international approval package for a variety of applications makes this unit suitable for nearly every situation SHORT FORM DATA Input voltage DC 12 48V 25...

Страница 2: ...with standard tolerances usually 15 included E g DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 24Vdc A figure with the unit Vdc at the end is a momentary figure wit...

Страница 3: ...by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50 of th...

Страница 4: ...e applied to the output continuously allowed Note 1 Each input can be loaded up to 10A At currents above 10A the other input should not be loaded It is preferable to parallel the two inputs in order t...

Страница 5: ...oltage drop when only one input draws current Voltage Drop U1 UOUT Not used or power supply with lower voltage V A QS10 241 24V 10A I1 U1 Output A V IOUT UOUT Variable Load 0 10A Input 1 Input 2 Outpu...

Страница 6: ...ears at 24V and 40 C min 25 years at 24V and 25 C MTBF SN 29500 IEC 61709 84 868 000h at 24V 40 C 125 266 000h at 24V 25 C MTBF MIL HDBK 217F 71 454 000h at 24Vand 40 C Ground Benign GB40 81 453 000h...

Страница 7: ...shipped in open position Fig 6 1 Connecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambien...

Страница 8: ...m Input 1 Input 2 Output 8 FRONT SIDE AND USER ELEMENTS Fig 8 1 Front side A Output terminals B Input terminals for input 1 C Input terminals for input 2 Apr 2014 Rev 1 3 DS MLY02 100 EN All parameter...

Страница 9: ...61000 4 8 50Hz 30A m Criterion A Criterions A Redundancy module shows normal operation behavior within the defined limits Notes A test is not applicable according to EN 61000 6 2 since the device does...

Страница 10: ...664 1 4 3 3 2 1 Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint sho...

Страница 11: ...ansient protection not included Internal input fuse not included 12 SAFETY FEATURES Input output separation no galvanic separation 200V epitaxial diode between input and output Safety level of output...

Страница 12: ...val for Canada CAN CSA C22 2 No 107 1 CAN CSA 60950 1 03 UL60950 1 HazLoc Class 1 Div 2 ANSI ISA 12 12 01 2007 LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems U S A ANSI I...

Страница 13: ...h 91mm to calculate the total required installation depth Installation clearances See chapter 2 Fig 14 1 Front view Fig 14 2 Side view 15 ACCESSORIES DIN Rail bracket for wall or panel mount A suitabl...

Страница 14: ...lies to the same value 16 2 INDUCTIVE AND CAPACITIVE LOADS The unit is designed to supply any kind of loads including unlimited capacitive and inductive loads 16 3 EXAMPLE 1 1 REDUNDANCY 1 1 Redundanc...

Страница 15: ...IN 2 I I I Note Use separate mains systems for each power supply whenever it is possible 16 5 EXAMPLE BATTERY BACK UP A battery back up requires one power supply and one MLY02 100 redundancy module Pl...

Страница 16: ...andard orientation Redundancy Module INPUT OUTPUT Output Current 0 10 20 30 40 60 C 2 6 8 10A 50 4 Ambient Temperature Fig 16 5 Mounting Orientation B Upside down Redundancy Module INPUT OUTPUT Output...

Отзывы: