MLY02.100
MiniLine
MLY-Series
DC12-48V
(120V),
10A,
D
UAL
R
EDUNDANCY
M
ODULE
10.
E
NVIRONMENT
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F)
Reduce output power above +60°C
Output de-rating
0.25A/°C
60-70°C (140°F to 158°F), see
Storage temperature
-40 to +85°C (-40°F to 185°F)
for storage and transportation
Humidity
**)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal
***)
2-17.8Hz:
±1.6mm
17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
***)
15g 6ms, 10g 11ms
3 bumps / direction
18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m (0 to 6 560ft)
without any restrictions
2000 to 6000m (6 560 to 20 000ft)
reduce output power or ambient temperature,
see Fig. 10-2
Altitude de-rating
0.7A/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 10-2
Over-voltage category
not applicable
The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation.
Fig. 10-1
Output current vs. ambient temp.
Fig. 10-2
Output current vs. altitude
Allowed Output Current
0
0
2000
4000
6000m
2.5
5.0
7.5
10.0
12.5
15.0
normal mode
Altitude
overload / short circuit
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
17.5A
Allowed Output Current
0
-40
0
20
40
70°C
2.5
5.0
7.5
10.0
12.5
15.0
60
-25
normal mode
at overload / short circuit
Ambient Temperature
17.5A
Apr. 2014 / Rev. 1.3 DS-MLY02.100-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
10/16