MLY02.100
MiniLine
MLY-Series
DC12-48V
(120V),
10A,
D
UAL
R
EDUNDANCY
M
ODULE
3.
I
NPUT AND
O
UTPUT
C
HARACTERISTICS
Number of inputs
-
2
Number of outputs
-
1
Input voltage
nom.
DC 12-48V
±25%
The input circuitry must meet the SELV requirements
stipulated by IEC/EN/UL 60950-1.
Input voltage range
-
9–60Vdc
Input voltage with restrictions
nom.
DC 12-120V
±25%
See note 3 on bottom of the table
Input voltage range
with restrictions
-
9-150Vdc
Restrictions apply, see note 3 on bottom of the table.
Voltage drop, input to output
typ.
0.8V
typ.
0.9V
at 1x5A, see Fig. 3-3
typ.
0.9V
at 2x5A, see Fig. 3-2
Input current
nom.
2x 0-5A
continuous
nom.
1x 0-10A
continuous, see note 1
nom.
2x 5-8A
for 5 seconds
Peak input current
max.
125A
for maximal 10ms per input
Output current
nom. 10A
continuous
nom.
10-16A
for 5 seconds
max.
16A at
continuous
overload
or short circuit, see note 2
Reverse current
max.
0.6mA
per input, -40°C to +60°C
Reverse voltage
max.
200Vdc
voltage applied to the output, continuously allowed
Note 1:
Each input can be loaded up to 10A. At currents above 10A, the other input should not be loaded. It is preferable to parallel the two
inputs in order to minimize the power loss in such cases.
Note 2:
Ensure that the continuous output current does not exceed 16A. Check the short-circuit current of the power sources and if the
power source can deliver more than 16A together, use an appropriate fuse on the output.
Note 3:
The redundancy module can be used with input voltages up to 150Vdc with the constraint, that it can be used only as a single input
module at voltages above 60Vdc. Both inputs need to be connected together as shown in Fig. 3-1. Ensure proper means to protect
against touching this voltage.
Fig. 3-1
Restrictions for utilizing voltages between 60 and 150Vdc (See also Note 3)
AC
DC
(>60V)
+
-
Load
>60V
+
-
Power Supply
Power Supply
Diode Module
+
-
+
+
-
-
AC
DC
(>60V)
+
-
AC
DC
(>60V)
+
-
Load
>60V
+
-
Power Supply
Diode Module
+
-
+
+
-
-
Diode Module
+
-
+
+
-
-
AC
DC
(>60V)
+
-
Power Supply
Apr. 2014 / Rev. 1.3 DS-MLY02.100-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
4/16