background image

 

 

PISA11.CLASS2

 

 

 

PISA11-Series 

P

ROTECTION 

M

ODULE 

24V,

 

4

 

O

UTPUTS

 

 

 

8.

 

O

UTPUT

-OK

 

R

ELAY 

C

ONTACT

 

This relay contact is closed when the input voltage is sufficient and the outputs are not shutdown.  

 

Threshold voltage 

typ. 

21.4Vdc 

Required voltage to power the relay and to close 
the relay contact. The outputs must also not be 
shutdown. 

Contact ratings 

max. 

30Vdc, 1.0A 

Resistive load 

 

max. 

30Vac, 0.5A 

Resistive load 

 min. 

1mA 

at 

5Vdc 

 

Galvanic isolation 

nom. 

500Vac 

Test voltage: Signal path to power path 

 

 

 

9.

 

ON/OFF

 AND 

R

ESET 

S

IGNAL 

I

NPUT

 

This signal input is galvanically isolated with an integrated optocoupler and works in the same manner as the reset 
and ON/OFF button. The ON/OFF function has no safety feature included. 

In a failure mode (outputs have shutdown), the outputs can be turned on again by 
applying a voltage for more than 1 second. 

12

 

(

+

)

5.1V

3mA

Inhibit

11

 

(

-

)

In normal mode (outputs have not shutdown), a short (> 50ms) voltage pulse will turn 
all outputs ON or OFF. 

The unit will be shipped (factory setting) with the outputs turned-on. 
 
Signal voltage 

max. 

30Vdc 

 

Signal current 

typ. 

3mA 

Active current limited 

 

max. 

6mA 

active current limited 

Threshold voltage levels 

min 

6Vdc 

Voltages above this level will trigger the inhibit or  

 max. 

10Vdc 

reset. 

Galvanic isolation 

nom. 

500Vac 

Test voltage: signal path to power path 

 

 

 

10.

 

S

YNCHRONIZATION OF 

M

ULTIPLE 

PISA

 

M

ODULES

 

If multiple PISA modules are used on the same power supply, it is recommended to connect the sync. bus of all 
modules together. If one unit shuts down due to the protection function of the input voltage protection circuit 
(safeguard), all other modules will shutdown too. This avoids a false interpretation of which output channel caused 
the problem. If the sync. terminals are not linked, the module with the highest safeguard protection voltage level 
(caused by tolerances) would shutdown 
first regardless whether the failure was 
caused by this module or not. 

1   2   3   4

Outputs

Input

+    

-    -

sync.

16
15
14
13
12
11

Reset

+

-

OK

PISA11

Input

L1  L2  L3  PE

QT40.241

Power
Supply

Output

+    

-

1   2   3   4

Outputs

Input

+    

-    -

sync.

16
15
14
13
12
11

Reset

+

-

OK

PISA11

1   2   3   4

Outputs

Input

+    

-    -

sync.

16
15
14
13
12
11

Reset

+

-

OK

PISA11

1   2   3   4

Outputs

Input

+    

-    -

sync.

16
15
14
13
12
11

Reset

+

-

OK

PISA11

Please note:  
If the cause for the shutdown was an over-
current of one individual channel only this 
module will shutdown and the other 
modules will stay on. In this case the sync. 
line has no impact on the other modules. 

Feb. 2012 / Rev. 1.3  DS-PISA11.CLASS2 - data sheet - 
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278-0    Germany 

9/19

Содержание Dimension PISA11 Series

Страница 1: ...n they are connected directly to the same power supply as the PISA module Less critical loads that are not affected to short voltage interruptions or that could even be the cause of a fault on the 24V...

Страница 2: ...6 1 ZM3 WALL Wall Mounting Bracket 19 The information presented in this document is believed to be accurate and reliable and may change without notice The housing is patent by PULS US patent No US D44...

Страница 3: ...ly so much current that the input voltage does not drop below 21V In case the input voltage would fall below this value e g due to overloads too small of a power supply or high inrush currents such as...

Страница 4: ...n power off before working on the device Protect against inadvertent re powering Make sure that the wiring is correct by following all local and national codes Do not modify or repair the unit Do not...

Страница 5: ...see Fig 5 1 output 3 nom 3 7A 3 2A see Fig 5 1 output 4 nom 3 7A 3 2A see Fig 5 1 All 4 outputs together nom 14 8A 12 8A Output current limitation min 16 6A 16 6A typ 19 9A 19 9A max 23 6A 23 6A Volt...

Страница 6: ...d output current At 2 times the rated current typ 1s at 7 4A At short circuit typ 10ms The timer for shutdown starts immediately once the rated current levels are exceeded All output channels will shu...

Страница 7: ...All four outputs will shutdown simultaneously Shutdown times for a short circuit condition across the outputs can be found in Fig 6 2 Fig 6 2 Active current limitation Period of time in current limit...

Страница 8: ...al values are defined with an additional resistive load See also the parameter list below the table Permissible Capacitors PISA11 CLASS2 Per channel 58mF 14mF All four outputs together typ 58mF min 14...

Страница 9: ...max 10Vdc reset Galvanic isolation nom 500Vac Test voltage signal path to power path 10 SYNCHRONIZATION OF MULTIPLE PISA MODULES If multiple PISA modules are used on the same power supply it is recomm...

Страница 10: ...his feature is also called return voltage immunity or resistance against Back E M F Electro Magnetic Force The protection module is resistant and does not show malfunctioning when a load feeds back vo...

Страница 11: ...ulated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value...

Страница 12: ...rotection function of the input voltage protection circuit all other modules will shutdown too This avoids a false interpretation of which output channel caused the problem If the cause for the shutdo...

Страница 13: ...a Use NEC Class 2 rated wires for the output b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and minimum 75 C for ambient up to 60...

Страница 14: ...ge voltage on input lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on output lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on...

Страница 15: ...y III IEC 62103 EN 50178 altitudes up to 2000m II for altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive Operational temperature is the same as the ambient temperatu...

Страница 16: ...F signal input and input output voltage are 1 3mm The following dielectric strength tests were conducted Fig 20 1 Dielectric strength A B C Type test 60s 500Vac 500Vac 50Vac Factory test 5s 500Vac 500...

Страница 17: ...rrent Protector Component Recognition UL Category QVRQ2 E File E342020 ANSI ISA 12 12 01 2007 Class I Div 2 Pending LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems NRTL C...

Страница 18: ...r PBDE Polychlorinated Diphenylether PCDE Polydibromphenyl Oxyd PBDO Cadmium Asbestos Mercury Silicia 24 READ OUT OF THE SOFTWARE REVISION LEVEL PISA utilizes a microcontroller with a dedicated firmwa...

Страница 19: ...AL DIMENSIONS AND WEIGHT Weight 120g 0 26lb DIN Rail Use 35mm DIN rail according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth to calculate t...

Отзывы: