PISA11.CLASS2

 

 

 

PISA11-Series 

P

ROTECTION 

M

ODULE 

24V,

 

4

 

O

UTPUTS

 

 

 

1.

 

I

NTENDED 

U

SE

 

This device is designed for installation in an enclosure and is intended for the general use such as in industrial control, 
office, communication, and instrumentation equipment. 

Do not use this device in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe 
personal injury or threaten human life. 

This device is designed for use in non-hazardous, ordinary or unclassified locations.  

 

 

 

2.

 

P

RODUCT 

D

ESCRIPTION

 

 

This protection module fulfills two basic functions. First it distributes the current of a large power source to four NEC 
CLASS 2 output channels and therefore allows for a simpler wiring method and easier approval process of the entire machine. 
The second function is to permit only so much current on the outputs that the input voltage of this unit (which 
corresponds to the output voltage of the power supply) does not fall below 21V. This ensures a reliable supply voltage 
for sensitive equipments, such as PLCs, controls or sensors, when they are connected directly to the same power supply 
as the PISA protection module. 

The protection module has one 24V input and four output channels to which the current is distributed. Each output 
channel is equipped with a redundant over-current protection, which avoids that wires will be overloaded. All four 
output channels will shutdown simultaneously, if the current of one individual channel or the maximum allowed 
current for the protection module is exceeded. 

A safeguard circuit in the input stage of the PISA module works like a valve. It permits only so much current that the 
input voltage does not drop below 21V. In case the input voltage would fall below this value (e.g. due to overloads, 
too small of a power supply or high inrush currents such as from starting a motor), all four output channels will be 
actively current limited and will shutdown after a certain period of time. 

A typical wiring configuration is shown below. All sensitive loads are connected directly to the power supply. If 
needed, these load circuits can be protected with standard circuit breakers or fuses. Loads which are less sensitive to 
voltage dips or interruptions or which are the source 
of the voltage drop themselves are connected to the 
output of the PISA protection module. 

Non NEC CLASS 2 Load

DC 24V

Power

Supply

NEC CLASS 2 Circuit 2

NEC CLASS 2 Circuit 3

NEC CLASS 2 Circuit 4

NEC CLASS 2 Circuit 1

A1

A2

A4

A3

PISA Protection Module

Safeguard

 

 

 

 

 

 

 

 

3.

 

I

NSTALLATION 

R

EQUIREMENTS

 

This protection module is suitable for DIN-rail mounting. Use DIN-Rails according to EN 60715 or EN 50022 with a 
height of 7.5 or 15mm. 

The protection module can be used with any regulated 24Vdc power supply. If the power source can deliver more than 
40A continuous, the PISA module shall be equipped with an external input fuse (e.g. 30/32A). The power capability 
and performance of the power supply can limit the output characteristics of the PISA module. 

Make sure that the input voltage polarity is correct before applying the input voltage. 

Do not connect batteries to the outputs of the PISA11 module. 

This device may only be installed and put into operation by qualified personnel.  

Feb. 2012 / Rev. 1.3  DS-PISA11.CLASS2 - data sheet - 
All parameters are specified at 24Vdc input, 25°C ambient temperature and a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278-0    Germany 

3/19

Содержание Dimension PISA11 Series

Страница 1: ...n they are connected directly to the same power supply as the PISA module Less critical loads that are not affected to short voltage interruptions or that could even be the cause of a fault on the 24V...

Страница 2: ...6 1 ZM3 WALL Wall Mounting Bracket 19 The information presented in this document is believed to be accurate and reliable and may change without notice The housing is patent by PULS US patent No US D44...

Страница 3: ...ly so much current that the input voltage does not drop below 21V In case the input voltage would fall below this value e g due to overloads too small of a power supply or high inrush currents such as...

Страница 4: ...n power off before working on the device Protect against inadvertent re powering Make sure that the wiring is correct by following all local and national codes Do not modify or repair the unit Do not...

Страница 5: ...see Fig 5 1 output 3 nom 3 7A 3 2A see Fig 5 1 output 4 nom 3 7A 3 2A see Fig 5 1 All 4 outputs together nom 14 8A 12 8A Output current limitation min 16 6A 16 6A typ 19 9A 19 9A max 23 6A 23 6A Volt...

Страница 6: ...d output current At 2 times the rated current typ 1s at 7 4A At short circuit typ 10ms The timer for shutdown starts immediately once the rated current levels are exceeded All output channels will shu...

Страница 7: ...All four outputs will shutdown simultaneously Shutdown times for a short circuit condition across the outputs can be found in Fig 6 2 Fig 6 2 Active current limitation Period of time in current limit...

Страница 8: ...al values are defined with an additional resistive load See also the parameter list below the table Permissible Capacitors PISA11 CLASS2 Per channel 58mF 14mF All four outputs together typ 58mF min 14...

Страница 9: ...max 10Vdc reset Galvanic isolation nom 500Vac Test voltage signal path to power path 10 SYNCHRONIZATION OF MULTIPLE PISA MODULES If multiple PISA modules are used on the same power supply it is recomm...

Страница 10: ...his feature is also called return voltage immunity or resistance against Back E M F Electro Magnetic Force The protection module is resistant and does not show malfunctioning when a load feeds back vo...

Страница 11: ...ulated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value...

Страница 12: ...rotection function of the input voltage protection circuit all other modules will shutdown too This avoids a false interpretation of which output channel caused the problem If the cause for the shutdo...

Страница 13: ...a Use NEC Class 2 rated wires for the output b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and minimum 75 C for ambient up to 60...

Страница 14: ...ge voltage on input lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on output lines EN 61000 4 5 DIN Rail 500V 1kV 500V 1kV Criterion A Criterion A Surge voltage on...

Страница 15: ...y III IEC 62103 EN 50178 altitudes up to 2000m II for altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive Operational temperature is the same as the ambient temperatu...

Страница 16: ...F signal input and input output voltage are 1 3mm The following dielectric strength tests were conducted Fig 20 1 Dielectric strength A B C Type test 60s 500Vac 500Vac 50Vac Factory test 5s 500Vac 500...

Страница 17: ...rrent Protector Component Recognition UL Category QVRQ2 E File E342020 ANSI ISA 12 12 01 2007 Class I Div 2 Pending LISTED for use in Hazardous Location Class I Div 2 T4 Groups A B C D systems NRTL C...

Страница 18: ...r PBDE Polychlorinated Diphenylether PCDE Polydibromphenyl Oxyd PBDO Cadmium Asbestos Mercury Silicia 24 READ OUT OF THE SOFTWARE REVISION LEVEL PISA utilizes a microcontroller with a dedicated firmwa...

Страница 19: ...AL DIMENSIONS AND WEIGHT Weight 120g 0 26lb DIN Rail Use 35mm DIN rail according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN rail height must be added to the unit depth to calculate t...

Отзывы: