Puls Dimension CP Series Скачать руководство пользователя страница 2

 

 

CP20.245-R2 

 

 

 

 

CP-Series 

24V,

 

20A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN  

All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

2/28 

 

I

NDEX

 

 
 

Page 

Page 

1.

 

Intended Use ....................................................... 3

 

2.

 

Installation instructions ...................................... 3

 

3.

 

AC-Input............................................................... 5

 

4.

 

DC-Input............................................................... 6

 

5.

 

Input Inrush Current ........................................... 6

 

6.

 

Output ................................................................. 7

 

7.

 

Hold-up Time ....................................................... 8

 

8.

 

DC-OK Relay Contact .......................................... 9

 

9.

 

Efficiency and Power Losses .............................. 10

 

10.

 

Lifetime Expectancy and MTBF ......................... 11

 

11.

 

Functional Diagram ........................................... 11

 

12.

 

Terminals and Wiring ........................................ 12

 

13.

 

Replacing Units while the System is Running .. 13

 

14.

 

Front Side and User Elements ........................... 14

 

15.

 

EMC .................................................................... 15

 

16.

 

Environment ...................................................... 16

 

17.

 

Protection Features ........................................... 17

 

18.

 

Safety Features .................................................. 17

 

19.

 

Dielectric Strength ............................................ 18

 

20.

 

Approved, Fulfilled or Tested Standards ......... 19

 

21.

 

Regulatory Product Compliance ...................... 20

 

22.

 

Physical Dimensions and Weight ..................... 21

 

23.

 

Accessories ........................................................ 22

 

23.1.

 

ZM10.WALL – Wall/Panel Mount Bracket 22

 

24.

 

Application Notes ............................................. 23

 

24.1.

 

Peak Current Capability ........................... 23

 

24.2.

 

Adjustment of the Output Voltage ......... 24

 

24.3.

 

Back-feeding Loads .................................. 25

 

24.4.

 

External Input Protection ......................... 25

 

24.5.

 

Output Circuit Breakers ............................ 25

 

24.6.

 

Series Operation ....................................... 26

 

24.7.

 

Parallel Use to Increase Output Power .... 26

 

24.8.

 

Parallel Use for Redundancy .................... 27

 

24.9.

 

Inductive and Capacitive Loads................ 28

 

24.10.

 

Operation on Two Phases ........................ 28

 

24.11.

 

Use in a Tightly Sealed Enclosure ............ 28

 

24.12.

 

Mounting Orientations ............................ 29

 

 

 
The information given in this document is correct to the best of our knowledge and experience at the time of 
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the 

word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is 
subject to revision. We therefore kindly ask you to always use the latest issue of this document. 
No part of this document may be reproduced or utilized in any form without our prior permission in writing. 
 
 
 

T

ERMINOLOGY AND 

A

BREVIATIONS

 

PE and 

 symbol

 

PE is the abbreviation for 

P

rotective 

E

arth and has the same meaning as the symbol 

Earth, Ground 

This document uses the term “earth” which is the same as the U.S. term “ground”. 

t.b.d.

 

To be defined, value or description will follow later. 

AC 230V 

A figure displayed with the AC or DC before the value represents a nominal voltage with 
standard tolerances (usually ±15%) included.  
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 

230Vac 

A figure with the unit (Vac) at the end is a momentary figure without any additional 
tolerances included.  

50Hz vs. 60Hz

 

As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency. 

may

 

A key word indicating flexibility of choice with no implied preference. 

shall

 

A key word indicating a mandatory requirement. 

should

 

A key word indicating flexibility of choice with a strongly preferred implementation. 

Содержание Dimension CP Series

Страница 1: ...systems and plug connector terminals to allow device replacement while the application keeps running The CP20 245 R2 covers an extreme wide temperature range from 40 C up to 60 C providing full outpu...

Страница 2: ...ed Enclosure 28 24 12 Mounting Orientations 29 The information given in this document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwis...

Страница 3: ...ons require a reduction in output current Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operating tempera...

Страница 4: ...me unless otherwise noted www pulspower com Phone 49 89 9278 0 Germany 4 28 The maximum surrounding air temperature is 70 C The operational temperature is the same as the ambient or surrounding air te...

Страница 5: ...1 65 1 63 1 63 At 20A Start up delay typ 450ms 420ms 440ms See Fig 3 2 Rise time typ 145ms 145ms 145ms At 20A const current load 0mF load capacitance see Fig 3 2 typ 160ms 160ms 160ms At 20A const cur...

Страница 6: ...r Supply AC DC Battery N a Use a battery or a similar DC source A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunction or damage the unit b Conne...

Страница 7: ...see Fig 6 3 The output voltage stays above 20V See chapter 24 1 for more peak current measurements Overload behaviour Continuous current Output voltage 13Vdc see Fig 6 1 HiccupPLUS mode Output voltage...

Страница 8: ...c behavior 12ms 0 0 4 8 12 28V 16 20 24 70A 30 10 40 50 20 60 Output Current 7 HOLD UP TIME AC 100V AC 120V AC 230V Hold up Time typ 65ms 65ms 65ms At 10A see Fig 7 1 min 54ms 54ms 54ms At 10A see Fig...

Страница 9: ...power supply in front of the decoupling device see also chapter 11 Contact closes As soon as the output voltage reaches typ 22Vdc Contact opens As soon as the output voltage dips below 22Vdc Short di...

Страница 10: ...n assumption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for anot...

Страница 11: ...ectrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors on...

Страница 12: ...mm2 max 6mm2 max 1 5mm2 American Wire Gauge AWG 20 12 AWG 24 10 AWG 26 14 Max wire diameter 2 4mm including ferrules 3 2mm including ferrules 1 8mm including ferrules Recommended tightening torque max...

Страница 13: ...system is running Load I I L N PE 1a L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input 1b 2a 3a 3b 2b Instructions...

Страница 14: ...8 0 Germany 14 28 14 FRONT SIDE AND USER ELEMENTS Fig 14 1 Front side A Input Terminals plug connector N L Line input PE Protective Earth input B Output Terminals plug connector Positive output Negati...

Страница 15: ...Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 Dips on the input voltage according to SEMI...

Страница 16: ...heric pressures from 80 47kPa Degree of pollution 2 acc IEC 61010 2 201 not conductive Vibration sinusoidal3 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis IEC 60068 2 6 Shock3 30g 6ms 20g 11ms 3 bumps dir...

Страница 17: ...y critical situations e g customer does not care about de rating requirements ambient temperature too high obstructs the airflow or install the unit in unsuitable mounting orientation There is no corr...

Страница 18: ...ng set the cut off current settings to the value in the table below Fig 19 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000Vac 1000Vac 500Vac Factory...

Страница 19: ...ble for US and Canada E File E198865 ATEX Agency Certificate Bureau Veritas EN 60079 0 Explosive atmospheres General requirements EN 60079 7 EN 60079 15 Equipment protection by type of protection e an...

Страница 20: ...according to VDMA 24364 C1 L W for solvents and water based paints 21 REGULATORY PRODUCT COMPLIANCE CE EU Declaration of Conformity Trade conformity assessment for Europe The CE mark indicates conform...

Страница 21: ...GHT Width 48mm Height 124mm without plug connectors Depth 127mm without plug connector The DIN rail depth must be added to the unit depth to calculate the total required installation depth DIN Rail Us...

Страница 22: ...23 ACCESSORIES 23 1 ZM10 WALL WALL PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall panel without utilizing the DIN Rail The bracket can be mounted without detaching the DIN ra...

Страница 23: ...to trip fuses on faulty output branches or to start peak current demanding loads Solenoids contactors and pneumatic modules often have a steady state coil and a pick up coil The inrush current demand...

Страница 24: ...haracteristic a setting to 24 0V results to an output voltage of 23 8V 0 2 at 24A and 25 0V 0 2 at no load See Fig 24 3 Output current min 24A At 45 C min 20A At 60 C min 15A At 70 C Reduce output cur...

Страница 25: ...AC supply systems and may also be used on 24V branches MCB s are designed to protect wires and circuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used...

Страница 26: ...load sharing between power supplies connected in parallel The Parallel use mode regulates the output voltage in such a manner that the voltage at no load is approx 4 higher than at nominal load See al...

Страница 27: ...individual power supply units Therefore use the built in DC OK relay contact of the power supply Fig 24 7 Wiring diagram 1 1 Redundancy for 20A output current 24V 20A Load L N PE Failure Monitor I I L...

Страница 28: ...phase to phase connection is allowed as long as the supplying voltage is below 240V 10 24 11 USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure the temp...

Страница 29: ...nded output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 24 9 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outpu...

Отзывы: