13.
R
EPLACING
U
NITS WHILE THE
S
YSTEM IS
R
UNNING
Fig. 13-1
Replacing the power supply or redundancy module while the system is running
Load
I
I
L
N
PE
1a
L N PE
+
-
CP20.241-R2-73
Power Supply
DC-OK
DC-
OK
Output 24V 20A
Input
L N PE
+
-
CP20.241-R2-73
Power Supply
DC-OK
DC-
OK
Output 24V 20A
Input
1b
2a
3a
3b
2b
Instructions:
-
Switch-off circuit breaker (1a).
-
Remove plug (2a).
-
Remove plug (3a). The plug prevents the cables from shorting.
-
Change power supply.
-
Put the plug (3a) back in.
-
Put the plug (2a) back in.
-
Turn-on the circuit breaker (1a).
-
The circuit is redundant again.
To replace the right power supply or redundancy module, use the same procedure but turn off circuit breaker (1b) and
remove plug / plug in (2b) and (3b).