CP20.245-R2
CP-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN
All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/28
Fig. 6-3
Dynamic overcurrent capability, typ.
Output Voltage
(dynamic behavior, < 12ms)
0
0
4
8
12
28V
16
20
24
70A
30
10
40
50
20
60
Output Current
7.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
65ms
65ms
65ms
At 10A, see Fig. 7-1
min.
54ms
54ms
54ms
At 10A, see Fig. 7-1
typ.
32ms
32ms
32ms
At 20A, see Fig. 7-1
min.
24ms
24ms
24ms
At 20A, see Fig. 7-1
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
10
20
30
40
80ms
85
120
155
190
230Vac
Input Voltage
50
60
Hold-up Time
20A, typ.
10A, min.
10A, typ.
70
20A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage