CP20.245-R2
CP-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN
All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/28
R
EDUNDANCY
P
OWER
S
UPPLY
AC 100-240V Wide-range input
Width only 48mm
Marine approvals, EMC Class B (bridge & deck)
Built-in decoupling MOSFET for 1+1 and N+1
redundancy
Efficiency up to 95.2%
20% Output power reserves (PowerBoost)
Safe Hiccup
PLUS
Overload Mode
Easy Fuse Breaking – 3 times nominal current for 12ms
Active power factor correction (PFC)
Full power between -40°C and +60°C
DC-OK relay contact
Current sharing feature included
3 Year Warranty
P
RODUCT
D
ESCRIPTION
The Dimension CP-Series are cost optimized power
supplies without compromising quality, reliability and
performance.
First of all, high immunity to transients and power surges
as well as low electromagnetic emission and Marine
approvals with EMC Class B make the
CP20.245-R2 the best choice for equipment in bridge &
deck zones the same way as for oil, gas and chemical
plants.
This power supply furthermore features a DC-OK signal
contact to remotely monitor error-free operation, a
decoupling MOSFET to set-up redundant power supply
systems, and plug connector terminals to allow device
replacement while the application keeps running. The
CP20.245-R2 covers an extreme wide temperature range
from -40°C up to +60°C providing full output power.
Outstanding features of CP20.245-R2 are its high
efficiency, the electronic inrush current limitation, and an
active PFC. The devices also offer PowerBoost: Power
reserves of 20%, which may even be used continuously at
temperatures up to +45°C. Additionally, the device can
deliver about 3 times the nominal output current for
12ms which helps to trip fuses on faulty output branches.
S
HORT
-
FORM
D
ATA
Output voltage
DC 24V
23.8 - 25.2V
Adjustment range
-
Output current
20A
Up to +60°C ambient
15A
At +70°C ambient
Derate linearly b60°C and +70°C
PowerBoost
24A
Up to +45°C ambient
Linear decrease to nominal power
b45°C and +60°C
Output ripple
max. 100mVpp 10Hz to 20MHz
AC Input voltage
AC 100-240V
-15%/+10%
Mains frequency
50-60Hz
±6%
AC Input current
4.28 / 2.25A
At 120 / 230Vac
Power factor
0.99 / 0.98
At 120 / 230Vac
AC Inrush current
10.0 / 4.5A
At 120 / 230Vac
Efficiency
93.8 / 95.2%
At 120 / 230Vac
Losses
31.7 / 24.2W
At 120 / 230Vac
Temperature range -40°C to +70°C
Hold-up time
32ms
Size w x h x d
48x124x127mm Without DIN-rail and
plug connectors
Weight
850g
O
RDER
N
UMBERS
Power Supply
CP20.245-R2
Mechanical Accessory
ZM10.WALL
Wall/Panel mount bracket
M
AIN
A
PPROVALS
For details and the complete approval list, see chapter 20.
UL61010-2-201
ATEX
IECEx
Marine