All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/28
17.
P
ROTECTION
F
EATURES
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection
typ. 30.5Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and performs three restart attempts. If the
failure continues for longer than 1s , the output shuts
down. Cycle input power to reset.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 5mm
E.g. screws, small parts
Over-temperature protection
yes **)
Output shut-down with automatic restart
Input transient protection
MOV
(Metal Oxide Varistor)
For protection values see chapter 15 (EMC).
Internal input fuse
included
Not user replaceable slow-blow high-braking capacity
fuse
*) In case of a protection event, audible noise may occur.
**) The temperature sensor is installed inside the isolating transformer and turns the unit off in safety critical situations (e.g. customer does
not care about de-rating requirements, ambient temperature too high, obstructs the airflow or install the unit in unsuitable mounting
orientation)
There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load and
installation methods.
18.
S
AFETY
F
EATURES
Input / output separation
*)
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 500MOhm
At delivered condition between input and output,
measured with 500Vdc
> 500MOhm
At delivered condition between input and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and PE,
measured with 500Vdc
> 500MOhm
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance
< 0.1Ohm
Resistance between PE terminal and the housing in the
area of the DIN-rail mounting bracket.
Touch current (leakage current)
typ. 0.32mA / 0.89mA
At 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.46mA / 1.27mA
At 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.73mA / 1.91mA
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.40mA / 1.07mA
At 110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.56mA / 1.53mA
At 132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.90mA / 2.34mA
At 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation